CyberPower Remote Management System
12
Battery
Low Battery Threshold
When the UPS supplies battery power and the remaining capacity is
lower than this threshold, the UPS will alarm.
External Battery Pack
Set the amount of external battery packs. This allows for an accurate
runtime estimation based upon the total number of batteries.
System
Cold Start
Set the ability of the UPS to start in the absence of input power.
When this option is enabled, the UPS can be turned on with battery
power.
Audible Alarm
If this option is enabled, the UPS will issue an audible alarm when
supplying battery power or when output is overloaded.
Dry Relay Function
This configures the power condition for the UPS dry relay to function
when the selected condition occurs. Refer to UPS manual for further
information about advanced UPS dry relay utilization. The Dry Relay
Function can be configured to be activated with following power
conditions:
(1)Utility Failure: The utility power fails and the UPS is using battery
power.
(2)Low Battery: The battery capacity is too low to support the
connected computers to shut down.
(3)Alarm: The UPS is issuing the audible alarm due to the
occurrence of warning events, such as overload.
(4)Bypass: The UPS has switched to Bypass mode due to overload
or UPS fault.
(5)UPS Fault: The UPS could be malfunctioning due to hardware
fault.
Screen Save Time
When no UPS button is pressed or no power event occurs during this
delay, the LCD screen will be turned off.
Wiring Fault Detecting
If this option is enabled, the UPS will detect if the UPS wiring is not
grounded or is reversed. It is recommended to assure the UPS wiring
has ground connection first. This option should be enabled if the UPS
wiring has ground connection.
Over Discharge
Protection
When the UPS is on Battery Mode with 0% load and the status
remains for the time configured, the RMCARD will enforce the UPS
to Sleep Mode and the output will be turned off.
Enter Sleep Mode After
All Clients Shutdown
If this option is enabled, UPS will enter sleep mode after utility power
failed and remaining MSDT+2 minutes. More information about
MSDT please reference to help page of UPS -> PowerPanel List.
Non-Critical Outlet Bank
Turn Off Threshold
When supplying battery power, the UPS will power off this NCL outlet