User`s manual
AT
RT
DT
OP
NE
Figure 5 – Header E5, RS-485 ‘RTS’ Enabled, with ‘Echo’
AT
RT
DT
OP
NE
Figure 6 – Header E5, RS-485 ‘DTR’ Enabled, with No Echo
Address and IRQ selection
The COML 106U is automatically assigned I/O addresses and IRQs by your motherboard BIOS. Only the I/O
address may be modified by the user.
Adding or removing other hardware may change the assignment of I/O addresses and IRQs.
Line Termination
Typically, each end of the RS-485 bus must have line-terminating resistors (RS-422 terminates at the receive end
only). A 120-ohm resistor is across each RS-422/485 data input in addition to a 1K-ohm pull-up/pull-down
combination that biases the receiver inputs. Header E4 allows customization of this interface to specific
requirements. Each jumper position corresponds to a specific portion of the interface. If multiple COML
106U adapters are configured in an RS-485 network, only the boards on each end should have jumpers T, P &
P ON. Refer to the following table for each position’s operation:
Name Function
P Adds or removes the 1K ohm pull-down resistor in the RS-422/RS-485 receiver circuit
P Adds or removes the 1K ohm pull-up resistor in the RS-422/RS-485 receiver circuit
T Adds or removes the 120 ohm termination.
L Connects the TX+ to RX+ for RS-485 two-wire operation.
L Connects the TX- to RX- for RS-485 two-wire operation.
COML 106U(-X)-D25 CyberResearch
®
Serial Communications
4 ©Copyright 2002 CyberResearch, Inc.