1.6 CYMOD RS-485 Network Configurations
CYMOD 400 Series is designed under RS-485 multi -drop network
architecture. Up to 256 CYMOD modules can be controlled in a multi -drop
network. The limit of 256 is due to command code. The network can be
connected by simple topology (Figure 1-1) or branch topology (Figure 1-2) or
free topology (Figure 1-3).
The CM 4520 and CM 4510 are the two basic communication modules to
construct a RS-485 network. The CM 4520 is a RS-232 to RS-485/RS-422
converter. The CM 4520 is used to build a RS-485 port for the host computer by
converting standard RS-232 signal into RS-485 signal.
The CM 4510 is the RS-485 signal repeater which is used to extend or to
lengthen the network distance. A CYMOD bus can connect up to 256 modules,
each segment is up to 128 modules. Whenever the numbers of the modules
excess 128, the repeater should be used. In addition, the length of a standard
RS-485 bus is up to 4000 feet, the repeater should be used whenever the
length of a signal bus is more than 4000 feet.
The CM 4530 is the USB to RS-485/RS-422/RS-232 converter, and it used to
build the USB signal into RS-485/RS-422/RS-232 signal.
The CM 4524 is an addressable RS-485/RS-422 to RS-232 converter, it allows
the RS-232 devices to easily link to the Host by the RS-485/422 bus.
Figure 1-1 Simple Topology
Host
RS-232/RS-485
CYMOD Modules
RS-232
RS-485 bus
CM 4520: RS -232 to
RS-485/RS-422
Converter
CM 4530 USB to
RS-232/RS485/RS-422
Converter.
Terminator
CM 4524