User`s manual
CYMOD 4531
•
51
5.2 Initialization & Installation
Software Installation
1. If CYMOD Administration is installed, skip the subsequent steps.
2. Backup your software diskette.
3. Insert the Administration disc into CD-ROM.
4. Change the drive path of CD-ROM to reflect your CD-ROMs assigned drive letter.
5. Find the setup of CYMOD Administration and run it.
6. Please follow the steps of setup program to succesfully install the Administration
software.
Objective of Initializing a Brand-New CYMOD 4531
All CYMOD modules except CYMOD 4520, 4510, and 4530, in a RS-485
network must have an unique address ID, however, every brand-new
CYMOD 4531 has a factory default setting as following:
♦ Address ID is 01.
♦ Baud rate is 9600 bps
♦ RS-485 Interface
♦ Host Watchdog timer is disable
Therefore, you must configure a new CYMOD unit before use,
otherwise the default address ID will conflict with other modules. The b aud
rate may also be changed according to user‘s requirements.
Default State
The CYMOD I/O modules must be set at Default State when you want to change
the default settings, such as the ID address, baud rate, check-sum status etc.
All CYMOD I/O modules have a special pin labeled as DEFAULT*. The module
will be in Default State if the DEFAULT* pin is shorted to ground when the power
is ON. In this state, the default configuration is set as following:
♦ Address ID is 00.
♦ Baud rate is 9600 bps.
♦ RS-485 Interface