User`s manual
CYMOD 4531
•
73
5.4.17 Open/Close Data Gate
@Description
Set the CM 4530 as non-addressable mode or addressable mode.
@Syntax
&(Addr)8(Data Gate Mode)<CR>
& Command leading code. (1-character)
(Addr) Address ID (2-character)
8 Open/Close Data Gate Command
Data Gate
Mode
10: Open the CM 4530 as non-addressable mode
00: Close the CM 4530 as addressable mode
@Response
!(Addr)<CR>
or
?(Addr)<CR>
@Example
User command: &30810<CR>
Response: !30
& Command leading code
30 Address ID
10 Open data gate
* Once the gate is open, the CM 4530 can be used as the CM 4520 for
transparent data converter.