Datasheet

www.cynergy3.com
© 2017 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
ISO
9001
CERTIFIED
Cynergy3 Components Ltd.
7 Cobham Road
Ferndown Industrial Estate
Wimborne, Dorset 21 7BH PE
SC-ISOSLICE-1 2017
Telephone +44 (0) 1202 897969
Email:sales@cynergy3.com
Made in the UK
SC-ISOSLICE-1
ISOLATED BUS I/O MODULE
2 off Universal Isolated Analogue I/O
Robust System with High MTBF
Very High Accuracy, Low Cost
Communicates to Ethernet / RS232 or RS485 network via an SC-E-100 unit
Inter-channel & Input/Output Isolation
Automatic Bus & Power Connection Via DIN Rail Bus Connector
The SC-ISOSLICE-1 isolated Bus I/O module
combines full three-port isolation with
access to an industrial bus. This bus
connects to the SC-E-100 modules which
are then used to transmit the process
values via either an Ethernet or a
RS232/485 wired communications network.
Full 3-port isolation is standard as is an
isolated transmitter supply which can be
used to power any standard 2-wire 4-20mA
transmitter.
The input type and range can be user
selected using simple DIL switches inside
the unit. All Thermocouple inputs are fully
linearised.
Non-interactive zero and span controls
make adjustment and calibration of the
unit quick and simple.
The units have a wide ranging 12 to 36 Vdc.
This supply can either be wired to the
appropriate terminals or picked up
automatically from the Bus connector.
Input Types for SC-ISOSLICE-1
DC/AC Current & Voltage
0-20mA, 4-20mA, 0-10mA into 15
Ω
0-1V, 0-10V, 1-5V into 1MΩ
Min & Max Full Scale Ranges are:
Thermocouples
Types E,J,K,N,R,S,T,B linearised or non-linearised. Ranges: Wide range of inputs. Cold junction
compensation. Upscale or downscale t/c burnout options. For 4-channel t/c input specify SC-
ISOSLICE-4
Outputs
For Output Modules see SC-ISOSLICE-6 or
SC-ISOSLICE-8
Technical Specifications
Parameter Min Typ Max Comments
Supply Voltage 12V 24V 36Vdc
Supply Current (mA) 45 90
For 24Vdc supply (260mA for 50ms on start-up)
Bus Connection 16-bit bus connection
Volt Drop (mA input) 0.3 At 20mA Input
Input Impedance (Volt) 1M Dependant on range (typ=10V)
Ω
Input Impedance (mA) 15 Dependant on range (typ=20mA)Ω
Output Linearity Error ±0.01% 0.05%±
Temp Coefficient ±50ppm/ºC
Time Constant (10-90%) 200mS
Operating Ambient 0ºC 55ºC
Relative Humidity 0% 90%
Isolation Voltage 1kV
see note
Surge Voltage 2.5kV for 50µS Transient of 10kV/µS
Notes
Absolute maximum ratings indicate sustained limits beyond which damage to the device may occur.
Device is protected against reverse polarity connection.
Accuracy figures based on 24Vdc supply, 4-20mA output with 250 load and an ambient 20ºC.
Ω
Installation Data
Mounting DIN Rail TS35
Orientation Any
Connections Screw Clamp with pressure plate
Conductor Size 0.5-4.0mm
Insulation Stripping 12mm
Weight Approx 95g
Ordering Information
Part No.: SC-ISOSLICE-1
Part Number
Universal
Inputs
mA or V
Inputs RTD Inputs T/C Inputs
Analogue
Out puts
Digita l
Inputs
Digita l
Out puts
SC-ISOSLICE-1 2
SC-ISOSLICE-2 8
SC-ISOSLICE-3 4
SC-ISOSLICE-4 4
SC-ISOSLICE-5 8
SC-ISOSLICE-6 4
SC-ISOSLICE-7
2xfreqin
SC-ISOSLICE-8 4
SC-ISOSLICE-9 4 x AC I/V
DC Current 0 - 1mA 0 - 20mA
DC Voltage 0 - 25mV 0 - 30V
Bipolar DC Voltage ±25mV ±10V
3 Wire Pot 0 - 10kΩ 0 - 100kΩ

Summary of content (1 pages)