SC-ISOSLICE-9
ISOLATED BUS I/O MODULE
4 off AC Current Inputs
Multiple inputs in one module
Very High Accuracy, Low Cost
Communicates to Ethernet / RS232 or RS485 network via an SC-E-100 unit
Input/Output/Power Supply Isolation
Automatic Bus & Power Connection Via DIN Rail Bus Connector
The SC-ISOSLICE-9 isolated Bus I/O module
combines full three-port isolation with
access to an industrial bus. This bus
connects to the SC-E-100 modules which
are then used to transmit the process
values via either an Ethernet or a
RS232/485 wired communications
network.
Full 3-port isolation is standard.
The SC-ISOSLICE-9 is designed to accept
current inputs from Current Transformers
with current outputs.
Non-interactive zero and span controls
make adjustment and calibration of the
unit quick and simple.
The units have a wide ranging 12 to 36 Vdc.
This supply can either be wired to the
appropriate terminals or picked up
automatically from the Bus connector.
Input Types for SC-ISOSLICE-9
AC Current
AC Current ranges
0-1Aac
Min & Max Full Scale Ranges are:
Outputs
For Output Modules see SC-ISOSLICE-6 or
SC-ISOSLICE-8
Technical Specifications
Parameter Min Typ Max Comments
Supply Voltage 12V 24V 36Vdc
Supply Current (mA) 45 90
For 24Vdc supply (260mA for 50ms on start-up)
Bus Connection 16-bit bus connection
Volt Drop 0.3 At 5A ac Input
Input Impedance (A) 0.2 Dependant on range (typ=0-1A)
Ω
Temp Coefficient ±50ppm/ºC
Time Constant (10-90%) 200mS
Operating Ambient 0ºC 55ºC
Relative Humidity 0% 90%
Isolation Voltage 1kV
see note
Surge Voltage 2.5kV for 50µS Transient of 10kV/µS
Notes
Absolute maximum ratings indicate sustained limits beyond which damage to the device may occur.
Device is protected against reverse polarity connection.
Accuracy figures based on 24Vdc supply, 4-20mA output with 250 load and an ambient 20ºC.
Ω
Installation Data
Mounting DIN Rail TS35
Orientation Any
Connections Screw Clamp with pressure plate
Conductor Size 0.5-4.0mm
Insulation Stripping 12mm
Weight Approx 95g
Ordering Information
Part No.: SC-ISOSLICE-9
Part Number
Universal
Inputs
mA or V
Inputs RTD Inputs T/C Inputs
Analogue
Out puts
Digita l
Inputs
Digita l
Out puts
SC-ISOSLICE-1 2
SC-ISOSLICE-2 8
SC-ISOSLICE-3 4
SC-ISOSLICE-4 4
SC-ISOSLICE-5 8
SC-ISOSLICE-6 4
SC-ISOSLICE-7
2xfreqin
SC-ISOSLICE-8 4
SC-ISOSLICE-9 4 x AC I/ V
DC Current 0-100mA 0 1A
AC Current 0-100mA 0 - 1A