SC4002ALM-6
Universal Input Dual Setpoint Trip Amplifier
Wide Range of User Configurable Inputs
Isolated Re-Transmission
Isolated Input Stage and Isolated Transmitter Supply
Configurable Trip Action and Fail-safe Mode
LED display of Input, Setpoints and Configuration
The SC4002ALM-6 trip-amplifier can
accept a wide range of inputs including 4-
20mA, thermocouple, RTD and voltage
types. The unit can have up to two relay
outputs and each can operate as a high or
low trip. The unit also produces an isolated
high level output.
The relay outputs are single pole change-
over relays with mains voltage rating. Each
trip can be configured so that the alarm
condition can be above or below the
setpoint. The relays can be energised or de-
energised in the alarm condition, satisfying
fail-safe and non-fail safe applications. In
addition the alarm LED's can be selected to
light when the relay is either on or off.
The input stage is isolated from the output
and power supply and the inputs can be
user-reconfigured for several different
ranges if specified at point of order. In
addition there is an optional isolated
transmitter supply of 24Vdc, suitable for
exciting most standard transmitters.
In addition numerous functions can be
selected using the built-in menus including
latching functions, delay on or delay off and
an alarm delay on power up.
If you require any other special function
please contact us on the number below.
The power supply is a wide ranging 16-
30Vdc supply
Inputs
DC Current and Voltage
0-20mA, 4-20mA, 0-10mA into 15 / 30
ΩΩ
0-1V, 0-10V, 1-5V into 100k / 1MΩΩ
Min and Max Full Scale Ranges:
DC Current 0 to 1mA 0 to 5A
DC Voltage 0 to 100mV 0 to 300V
Note: For input voltages greater than 60Vdc a
Divider unit must be specified.
Thermocouples
Types E,J,K,N,R,S,T & B linearised or non-linearised
Ranges Wide range of inputs
Auto cold junction compensation.
Upscale or downscale t/c burnout options.
Resistance Thermometers
2, 3 or 4 wire PT100 or PT1000, linearised (or not)
Ranges Wide range of inputs (Up or downscale b/o)
Outputs
Mains Rated Relays
3A resistive at 240V ac
DC Current and Voltage
0-20mA, 4-20mA, 0-10mA into 750
Ω
0-1V, 0-10V, 1-5V into a minimum 2kΩ
Technical Specifications
Parameter Min Typ Max Comments
Supply Voltage 16V 24V 30V
Supply Current (mA) 24 110
24Vdc supply, max if both relays energised
Volt Drop (mA input) 3V At 20mA Input on 0-20mA range
Input Impedance (Volt) 1M
Ω
Input Impedance (mA) 15Ω
Temp Coefficient ±100ppm/ºC
Relay Response Time 10ms
Operating Ambient 0ºC 55ºC
Relative Humidity 0% 90%
Isolation Voltage 1kV
see note
Surge Voltage 2.5kV for 50µS Transient of 10kV/µS
Notes
Setpoints are configured on the LED display on the front panel.
H/H,H/L, L/H, LL, fail-safe, non-fail safe and hysteresis options are set using the display.
Figures based on 24Vdc supply @ 20ºC ambient
Installation Data
Mounting DIN Rail TS35
Orientation Any
Connections Screw Clamp with pressure plate
Conductor Size 0.5-4.0mm
Insulation Stripping 12mm
Weight Approx 140g
Ordering Information
Part No.: SC4002ALM-6
Term. Connection
3
5
4
6
10
Output -ve 18 Relay 1 N/C
12 Output +ve 19 Relay 1 N/O
20 Relay 1 Common
1 Power Input –ve 15 Relay 2 N/C
2 Power Input +ve 16 Relay 2 N/O
17 Relay 2 Common
Tx Supply +ve, RTD 4
th
Wire
Input mA, V, T/C, RTD +ve
Input mA, V, T/C, RTD -ve
RTD 3
rd
Wire