The CTM-130/132 modem has 6 user inputs and 4 user outputs. The inputs may be configured for either
digital or analog monitoring configuration of this and their use to trigger reporting can be set on the
I/O page.
In order to use an input as a report trigger it is necessary to configure it for the desired operation:
First select if the input is a Digital or Analog type - digital inputs are simple On or Off decisions based
on a voltage threshold of 2.5V +/- 0.5 V, while analog inputs have a range of 0 to 10V.
Next select if the input logic is Positive or Negative: for positive logic an analog input voltage greater
than the set threshold or a digital input of greater than 3.0V will be deciphered as On for report
triggering; for negative logic an analog input voltage less than the set threshold or a digital input of
less than 2.0V will be deciphered as On for report triggering.
For analog inputs set the Threshold voltage at which you wish the report to be triggered.
Lastly set the reporting trigger On, Off, or Change: On will trigger continuous reports while the
input is in the On state; Off will trigger continuous reports while the input is in the Off state; Change
will trigger a single report whenever the input changes state from On to Off, or Off to On.
The 4 digital outputs may be controlled from this page: each output may be set as On or Off to control
equipment that is connected to the CTM-130/132 modem.