Installation Manual
English 23
Installation requirements
Electrical Connection
For proper installation, you must determine th
e type of electrical connection you will
use and follow the directions in this manual.
• The oven must be connected to the proper electrical voltage and frequency as given
on the model/serial/rating plate, which is on the bottom-left door trim.
Model/serial/
rating plate
Single Oven Double Oven
• A circuit breaker is recommended.
• Use this chart to determine the minimum recommended dedicated circuit protection.
KW Rating (240 V) KW Rating (208 V)
Recommended Circuit Size
(Dedicated)
≤4.8 KW ≤4.1 KW 20 Amp
4.9 KW - 7.5 KW 4.3 KW - 6.2 KW 30 Amp
7.3 KW - 9.6 KW 6.3 KW - 8.3 KW 40 Amp
9.7 KW - 12.0 KW 8.4 KW - 10.4 KW 50 Amp
• Connect directly to the circuit-breaker box (or fused disconnect) through flexible,
armored- or nonmetallic-sheathed, copper cable with ground wire. (See Electrical
Connection.
Model/serial/
rating plate