Installation Guide

8 English
Preparation
Preparation
Electrical Connection
To properly install your oven, you must determine the type of electrical connection
you will be using and follow the instructions provided in this manual.
Oven must be connected to the proper electrical voltage and frequency
as specied on the model/serial/rating plate. The model/serial/rating
plate is located below the control panel on combi ovens. See the following
illustrations.
A
Combi. oven
A. Model/serial/rating plate
A circuit breaker is recommended.
Use the chart below to determine the minimum recommended dedicated
circuit protection.
KW Rating (240 V) KW Rating (208 V)
Recommended Circuit
Size (Dedicated)
≤4.8 KW ≤4.1 KW 20 Amp
4.9 KW - 7.5 KW 4.3 KW - 6.2 KW 30 Amp
7.3 KW - 9.6 KW 6.3 KW - 8.3 KW 40 Amp
9.7 KW - 12.0 KW 8.4 KW - 10.4 KW 50 Amp
Connect directly to the circuit breaker box (or fused disconnect) through
exible, armored or nonmetallic sheathed, copper cable (with grounding wire).
See “Electrical Connection” section.
Flexible conduit from the oven should be connected directly to the junction
box.
Fuse both sides of the line.
Do not cut the conduit. The length of conduit provided is for serviceability of
the oven.
A UL listed or CSA approved conduit connector must be provided.
If the house has aluminum wiring, follow the procedure below:
1. Connect a section of solid copper wire to the ends of the exible conduit
leads.
2. Connect the aluminum wiring to the added section of copper wire using
special connectors and/or tools designed and UL listed for joining copper
to aluminum.
Follow the electrical connector manufacturer’s recommended procedure.
Aluminum/copper connection must conform with local codes and industry
accepted wiring practices.
For power requirements for models DOC30P977D* refer to the following table.
Model
240 VAC 208 VAC
Power Circuit size Power Circuit size
DOC30P977D* 8.9 kW 40 Amp 6.7 kW 30 Amp
Install_DOC30P977D_DG68-01317A-00_EN+MES+CFR.indb 8 2020-06-30 �� 4:51:34