Installation Manual
Table Of Contents
- Before you begin
- Important safety information
- Gas range components
- Installation requirements
- Tools and materials
- Installation instructions
- Antes de comenzar
- Información importante de seguridad
- Lea todas las instrucciones antes de usar este electrodoméstico
- Símbolos usados en este manual
- California Proposición 65 Advertencia
- Mancomunidad de Massachusetts
- Seguridad general
- Seguridad contra incendios
- Seguridad del gas
- Seguridad de la electricidad y la conexión a tierra
- Seguridad de la instalación
- Seguridad de la ubicación
- Seguridad de la cubierta
- Seguridad del horno
- Seguridad durante la auto-limpieza del horno
- Componentes de la estufa a gas
- Requisitos de instalación
- Herramientas y materiales
- Instrucciones de instalación
- Avant de commencer
- Informations importantes relatives à la sécurité
- Lisez toutes les consignes de sécurité avant d'utiliser cet appareil
- Symboles utilisés dans ce manuel
- California Proposition 65 Avertissement
- Commonwealth du Massachusetts
- Sécurité générale
- Sécurité incendie
- Sécurité liée au gaz
- Sécurité électrique et mise à la terre
- Sécurité liée à l'installation
- Sécurité de l'emplacement
- Sécurité liée à la table de cuisson
- Sécurité liée au four
- Sécurité liée à l'auto-nettoyage du four
- Composants de la cuisinière à gaz
- Conditions d'installation
- Outils et matériel
- Consignes d'installation
20 English
Installation instructions
Installation instructions
Specied power-supply-cord kit rating
Range rating, watts
Specied rating
of power-supply-
cord kit, amperes
Diameter (inches) of range
connection opening
120/240
volts 3-wire
120/208
volts 3-wire
Power cord Conduit
8750 - 16500 7801 - 12500 40 or 50 A 1⅜" 1⅛"
Step 4. Installing the power cord
For power cord installations, hook the strain relief over the power cord hole (1⅜")
located below the rear of the drawer body. Insert the power cord through the
strain relief and tighten the device.
• You must install the power cord with a strain relief.
• Attach the strain relief to the 1⅜" opening in conduit connection plate.
A 50 amp range cord is not recommended but if used, it should be marked for
use with nominal 1⅜" diameter connection openings. Care should be taken to
center the cable and strain relief within the knockout hole to keep the edge from
damaging the cable.
Because range terminals are not accessible after range is in position, exible
service conduit or cord must be used.
NOTE
If conduit is being used, go to Step 5 on pages 22–23.
ALL NEW BRANCH-CIRCUIT CONSTRUCTIONS, MOBILE HOMES,
RECREATIONAL VEHICLES AND INSTALLATIONS WHERE LOCAL
CODES DO NOT ALLOW GROUNDING THROUGH NEUTRAL, REQUIRE A
4-CONDUCTOR UL-LISTED RANGE CORD.
Step 3. Accessing the power cord connection
Remove the rear access cover and loosen the screw with a screwdriver. The
terminal block will then be accessible.
Terminal block
Access cover