Manual de servicio Acondicionador de Aire Tipo Ventana Modelo: DWA-182R
Contents CONTENTS 1. Specifications ................................................................................................2 2. Operation .....................................................................................................3 3. Wiring Diagram..........................................................................................10 4. Refrigerant Cycle .........................................................................................11 5. Control Block Diagram..............
1. SPECIFICATIONS MODEL ITEM Power source DWA-182R V/Hz AC 220V, 60Hz Btu/h 18,000 Kcal/h 4,540 Btu/wh 8.8 Kcal/wh 2.2 L/h 2.3 Cooling Capacity Energy Efficiency Ratio Dehumidification Power Input(W) 2,040 Electrical Data Running Current(A) Compressor 9.
2.
2 REMOTE CONTROLLER REMOCON SIGNAL TRANSMITTER TIMER/CANCEL • Everytime you push this button, timer is set as follow. (1Hr→2Hr→3Hr→4Hr→5Hr→6Hr→8 Hr→10Hr→12Hr→16Hr→20Hr→24Hr →CANCEL). After the unit is timed, if this button is pushed, timer is canceled. TIMER/ CANCEL FAN SPEED SLEEP • SLEEP mode is selected as follow. (L1→L2→Cancel) SLEEP AUTO SWING FAN SPEED • Everytime you push this button, it is selected as follow.
3 REMOTE CONTROLLER DISPLAY MODE DISPLAY • It displays the operating mode. TEMP./TIMER DISPLAY • It displays the temperature and the timer. REMOCON SIGNAL RECEIVER TEMPERATURE SET BUTTON • It is the button to set the desired room temperature.
Replacing Batteries 1 Remove the COVER from the back of the remote controller. • Slide the cover according to the arrow direction 2 Insert two battaries. • Be sure that the (+) and (–) directions are correct • Be sure that both batteries are new – + 3 Re-attach the cover. • Slide it back into position + – • Do not use rechargeable batteries such batteries differ from standard dry cells in shape, dimensions and performance.
4 DESCRIPTION OF FUNCTIONS OFF-Timer If you set time in OFF-Timer Mode, the unit will stop at the set time. ON Unit ON Unit OFF OFF SET Time HOUR ON-Timer If you set time in ON-Timer Mode, the unit will run at the set time.
Fan Speed (1) Motor speed (high speed, normal speed, low speed). (2) Remote controller setting fan speed. (H, M, L) (3) Relation of operating mode between fan speed. FAN ONLY COOL TURBO H H H H M M M - L L L - Sleep Mode (1) When you are going to sleep, select sleep button in remocon and the unit controls the room to the desired temperature. (The unit will not operate after 4 hour) (2) For changing the temperature.
Auto Swing (1) When you push this button, in remocon the left/right flap move to the position of keeping the room temperature comiortable. (2) The air discharge direction procedure is below. Auto swing Fixed Turbo Mode(Powerful Cooling) (1) Cooling Condition 1 Fan Speed: High speed 2 Set temperature:16˚C(Fixed) 3 Compressor and Fan ON OFF (Room temperature-18˚C) -1 0 1 Self-Diagnostic Function The control will contain diagnostic test to verify the integrity of the system.
3. WIRING DIAGRAM E D CN4 1 2 1 2 CN2 CN5 1 2 3 4 1 2 3 4 5 6 7 8 M B 1 2 3 4 5 6 7 8 9 10 SWING MOTOR BLK RED GRY YEL CAPACITOR FAN ORG MOTOR ORG I GRN(GRN/YEL) N P RL1 C 3 4 B R C BRN COMP O.L.
4.
5.
6.
Part List MAIN PCB ASS'Y(3104302500) NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 PART NAME IC MICOM IC DRIVE IC DRIVE IC REGULATOR IC REGULATOR IC RESET FUSE CLIP FUSE RELAY RELAY POWER RESONATIOR VARISTOR DIODE DIODE HEAT SINK PCB BUZZER TR WAFER WAFER WAFER WAFER WAFER WAFER WAFER WAFER PIN RESISTOR RESISTOR RESISTOR RESISTOR RESISTOR RESISTOR RESISTOR ARRY RESISTOR ARRY C-ELEC C-ELEC C-ELEC C-ELEC C-ELEC C-CERA TMP47P443N TD62004A
Front PCB ASS'Y' (3104302400) NO 1 2 3 4 5 6 7 8 9 10 11 PART NAME LED DISPLAY C-CERA RECEIVE MODULE LED LED SWITCH TACT DIODE WAFER WAFER PCB JUMPER SPEC 88 103Z 50VDC PIC-26043TH2 DLSO-5031D DLG-5031D JTP1212 1N4148 SMAW250-08 SMAW250-10 FR-1 10mm PART CODE 3103003700 CXCH1H103M 1PC26043TH DDLS05031D DDLG5031D3109300900 DZN4148A-3108804800 3108802400 3104302200 3109400100 QÕ TY 1 1 1 3 3 6 6 1 1 1 7 REMARK DISP C1 REMO PART CODE 3101100510 3101100600 3101405900 3105100600 3105100700 3105100800 31084
7. TROUBLE SHOOTING Self-Diagnostic Function 1) Error Code 1(Er) 1 Check the connector of room air thermistor. (or connecting wire) 2 Check soldering of connecting on control P.C.B. (Error of soldering or short) 3 Check the resistance of room air thermistor. “Press the temperature Keys (Up & Down), Error code is displayed.” Unit Not Run The power is applied to the unit Rating voltage Check the voltage between “POWER 1 ” and “RL1 4 ” of Main P.C.
Only Compressor Do not Run - Check the following at cooling mode Check the voltage between “POWER 1 ” and “RL1 3 ” of Main P.C.B Rating voltage less than 90% Check the Main P.C.B the circuit for relay driving. Rating voltage more than 90% Rating voltage less than 90% Check the compressor wiring Check the connecting wire between Main P.C.
PCB DRIVING DESCRIPTION
Power Supply(1) C1 335 AC 220V + VAR1 C2 2200/35V POWER TRANS 3 C6 0.1 + C7 7805 2 1 3 C4 0.1 100/16V + C5 7812 2 470/25V 1 C3 104 DESCRIPTION DC Power Supply in circuit needs +12V and +5V. +12V is used for Compressor Driving Relay, Fan Motor Driving Relay, Buzzer Driving, Swing Motor Driving Relay and LED Display. AC voltage of secondary Power Transformer is rectified by 4 Diode, and it is filtering by Main Condensor C2.
Oscillation(2) 1 MICOM 2 8 MHz DESCRIPTION Oscillatory Frequency drive Micom, it is made up 8MHz resonator oscillatory Freqency. Ocillatory wave is as following Fig 2-1.
Sensor(3) Room temperature Sensor Input Vcc ROOM:PT-K43C 2 MICOM R4 15 1 300 C13 0.01 R3 12.7K DESCRIPTION Number 15 of Micom is Terminal of A/D convertor Input. Room temperature is sensing by change of Thermister Resistance, Micom is put in 5V by ratio between R3 (12.7KΩ) and Room sensor. Relation between temperature and voltage is following Table 3-1. C13 is Noise filter. Temperature (°C) Voltage (V) No. 15 -10 4.06 0 3.60 15 2.76 25 2.20 40 1.
Remote Controller(4) DESCRIPTION Signal from Remote Controller put in only Control Data Signal at Micom Terminal of Number 5, which is gotten field of Carrier (38KHz) from Receive Module. Signal Wave repeat third as following Fig 5-1. But in Secondary Wave Custom Code is Reversed Face. 9ms 4.5ms LEADER CODE 16bit 16bit CUSTOM CODE DATA CODE Fig 5-1 0.56ms 0.56ms 1.12ms bit 0 2.
Micom Power Supply(5) Vcc 5V 28 MICOM C10 100µF/16V 6 C9 104 14 DESCRIPTION MICOM Power is supplied 5V at Number 28 using VDD, Number 6 using Analog Reference of A/D Converter. C9, C10 is Ripple filter.
Reset(6) 5V 5V R1 5.6K MICOM 3 3 + C11 1µF/50 7042 2 1 RESET IC DESCRIPTION Voltage less than about 4.2V put in Micom Terminal of Number 6 and then Micom reset. Reset IC detect Power ON and Voltage greater than 4.2V, and then send Reset Signal. Vcc (+5V) 4.
Function Selecting(7) +5V MICOM TEST 27 ˚F/ ˚C 13 R3 10K R2 10K DESCRIPTION Selecting Function is as following table 9-1.
8.
(3) U2(TD62004AP) DARLINGTON ARRAYS IN1 1 IN2 2 IN3 3 IN4 4 IN5 5 IN6 6 IN7 7 GND 8 16 OUT 1 15 OUT 2 14 OUT 3 13 OUT 4 12 OUT 5 11 OUT 6 10 OUT 7 9 COMMON FREE WHEELING DIODES KID65004AP COM 10.5K 7.2K 3K (Equivalent Circuit) (Top View) (4) U7 (7805CT): VOLTAGE REGULATOR (5VDC) SCHEMATIC DIAGRAM TSUFFIX PLAASTIC PACKAGE CASE 221A TO-220TYPE INPUT 100K 100 100 500 10K 240 200 3.3 K 1 2 3 1.4 K Pin 1. INPUT 2. GROUND 3. OUTPUT OUTPUT 2K 6K 2.7 K 0.3 0.
9. DISASSEMBLY INSTRUCTIONS Please refer to the chapter 10 (Exploded diagram and parts list). 1 2 Before service of 1. Stop the unit, remove the power cord from the receptacles. any part. 2. Move the unit to the safe location for the suitable work. Ass’y Fan Motor 1. Remove Front Grille - Fan Motor - Remove Filter Pre. - Propeller Fan - Remove screw(2 point) in Front Grille. - Blower Fan 2. Remove Cabinet from the unit. - Remove screws (2 point) from the unit’s sides. 3. Remove Holder Scroll.
10. EXPLODED DIAGRAM AND PARTS LIST ■ DWA-182R PART LIST ✔ Caution: In this Service Manual, some parts can be changed for improving, their performance without notice in the parts list. So, if you need the latest parts information, please refer to PPL(Parts Price List) in Service information Center(http://svc.dwe.co.kr) No.
No. CODE 39 3100068402 AS PIPE COND IN (A) 1 C1220T-0D 7.94 40 3100068420 AS PIPE COND OUT (A) 1 C1220T-0D 9.52 41 3104429610 AS PIPE COND IN (C) 1 C1220T-0D 7.
* DWA-182R
DAEWOO ELECTRONICS CO., LTD. 686, AHYEON-DONG MAPO-GU SEOUL, KOREA C.P.O. BOX 8003 SEOUL, KOREA TELEX: DWELEC K28177-8 CABLE: “DAEWOOELEC” FAX: 02) 590-6291 TEL: 02) 360-7114/590-6151~5 http://www.dwe. daewoo.co.kr S/M NO.: DWR182R010 PRINTED DATE: JULY.