Daikin AHKD Installation Manual

3
DAR0904 Temperature Rise Table (Degrees F)
208 240 480
2800 14 19 19
2900 14 18 18
3000 13 18 18
3100 13 17 17
3200 12 17 17
2800 19 25 25
2900 18 24 24
3000 18 24 24
3100 17 23 23
3200 17 22 22
2800 28 38 38
2900 27 37 37
3000 27 35 35
3100 26 34 34
3200 25 33 33
Airhandler
Heat Kit
KW
CFM
Supply Voltage
15
20
DAR0904
Temperature
Rise Table
(Degrees F)
30
Table 4.
DAR1204 Temperature Rise Table (Degrees F)
208 240 480
3800 10 14 14
3900 10 14 14
4000 10 13 13
4100 10 13 13
4200 9 13 13
3800 14 19 19
3900 14 18 18
4000 13 18 18
4100 13 17 17
4200 13 17 17
3800 21 28 28
3900 20 27 27
4000 20 27 27
4100 19 26 26
4200 19 25 25
CFM
Supply Voltage
DAR1204
Temperature
Rise Table
(Degrees F)
15
20
30
Airhandler
Heat Kit
KW
Table 5.
NOTE: Table 5 is calculated with both stages of electric heat en-
gaged (2 stage heat systems). For systems using staged electric
heat, divide the temperature rise from the table by 2 for 1
st
stage
operation.
E
LECTRICAL
S
UPPLY
W
IRE
AND
MOP
T
O
AVOID
THE
RISK
OF
FIRE
OR
EQUIPMENT
DAMAGE
,
USE
COPPER
CONDUCTORS
ONLY
.
WARNING
T
O
AVOID
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRICAL
SHOCK
,
THIS
UNIT
MUST
HAVE
AN
,
ELECTRICAL
GROUND
. T
HE
ELECTRICAL
GROUND
CIRCUIT
MAY
CONSIST
OF
AN
APPROPRIATELY
SIZED
ELECTRICAL
WIRE
CONNECTING
THE
GROUND
LUG
IN
THE
UNIT
CONTROL
BOX
TO
THE
BUILDING
ELECTRICAL
SERVICE
PANEL
.
O
THER
METHODS
OF
GROUNDING
ARE
PERMITTED
IF
PERFORMED
IN
ACCORDANCE
WITH
THE
N
ATIONAL
E
LECTRIC
C
ODE
(NEC)/A
MERICAN
N
ATIONAL
S
TANDARDS
I
NSTITUTE
(ANSI)/N
ATIONAL
F
IRE
P
ROTECTION
A
SSOCIATION
(NFPA) 70
AND
LOCAL
/
STATE
CODES
. I
N
C
ANADA
,
ELECTRICAL
GROUNDING
IS
TO
BE
IN
ACCORDANCE
WITH
THE
C
ANADIAN
E
LECTRIC
C
ODE
(CSA) C22.1.
UNINTERRUPTED
UNBROKEN
WARNING
INSPECTION OF THE BUILDING ELECTRICAL SERVICE.
T
HIS
UNIT
IS
DESIGNED
FOR
3-
PHASE
OPERATION
. DO NOT OPERATE
ON A SINGLE PHASE POWER SUPPLY. SEE THE “WARNING“
ABOVE.
M
EASURE
THE
POWER
SUPPLY
TO
THE
UNIT
. T
HE
SUPPLY
VOLTAGE
MUST
BE
IN
AGREEMENT
WITH
THE
UNIT
NAMEPLATE
POWER
REQUIREMENTS
AND
WITHIN
THE
RANGE
SHOWN
IN
T
ABLE
6.
WARNING
Building Electrical Service Inspection
This unit is designed for 3-phase operation. DO NOT OPERATE
ON A SINGLE PHASE POWER SUPPLY. SEE THE PRECEDING
WARNING. Measure the power supply to the unit. The supply
voltage MUST be in agreement with the unit nameplate power
requirements and within the range shown in Table 6.
Minimum Supply Maximum Supply
Voltage Voltage
208 – 230 187 253
460 414 506
Nominal
Table 6.
Voltage Balance The supply voltage shall be unbalance (phase to
phase) within 2%. To calculate the percentage of voltage unbalance
use the following formula:
Percentage Max Voltage Deviation From Avg Volt-
age Unbalance = 100 x Average Voltage
Example
. L1 – L2 = 220 V
L2 – L3 = 216 V
L1 – L3 = 213 V
Avg. Voltage = (220+216+213) / 3
= 649 / 3
= 216
Max. Deviation from Avg. = 220 – 216 = 4
% Voltage Unbalance = 100 x (4 / 216)
= 400 / 216
= 1.8%