Daikin DP14CM Installation Manual

6
When installing filters, ensure the air flow arrows on the filter are point-
ing toward the circulator blower.
Refer to the unit filter size chart below for filter size information.
NOMINAL SIZE
(INCHES)
NOMINAL AREA
(SQ. FT.)
10x20 1.4
14x20 1.9
14x25 2.4
15x20 2.1
16x20 2.2
16x25 2.8
20x20 2.8
20x25 3.5
25x25 4.3
MINIMUM FILTER SIZE
NOTE: Filters must have adequate face area for the rated quantity
of the unit. See the air delivery table below for recommended
filter size. Size the filters in accordance with their manufacturer
recommendations. Throwaway filters must be sized for a maxi-
mum face velocity of 300 feet per minute.
500 1000 1500 2000 2500 3000 3500
7
6
5
4
3
2
D
I
S
P
O
S
A
B
L
E
F
I
L
T
E
R
P
E
R
M
A
N
E
N
T
F
I
L
T
E
R
Airflow - SCFM
N
o
m
i
n
a
l
F
i
l
t
e
r
A
r
e
a
S
q
u
a
r
e
F
e
e
t
PIPING
CONDENSATE DRAIN
The condensate drain connection of the evaporator is a half coupling of
¾” N.P.T. A trap must be provided to have Proper condensate drainage.
2" Minimum
3" Minimum
A Positive Liquid Seal
Is Required
Flexible
Tubing-Hose
Or Pipe
Drain
Connection
Unit
Install condensate drain trap as shown. Use ¾ “ drain connection
size or larger. Do not operate without trap. Unit must be level or
slightly inclined toward drain.
WIRING
NOTE: All wiring should be made in accordance with the National
Electrical Code.
Consult your local Power Company to determine the availability of
sufficient power to operate the unit. Check the voltage, frequency,
and phase at the power supply to ensure it corresponds to the
units RATED VOLTAGE REQUIREMENT.
In accordance with the N.E.C. or local codes, install a branch circuit
fused disconnect near the unit. Determine wire sizes and overcur-
rent protection from the unit nameplate ampacity and in accor-
dance with the Branch Circuit Ampacity table on the next page or
the N.E.C. The wiring should never be sized smaller than is recom-
mended by either of these two sources.
Fuses smaller than that recommended on the rating plate could result in
unnecessary fuse failure or service calls. The use of protective devices of
larger size than indicated could result in extensive damage to the equip-
ment. The manufacturer bears no responsibility for damage caused to
equipment as result of the use of larger than is recommended size pro-
tective devices.
All units have undergone a run test prior to packaging for shipment. This
equipment has been started at minimum rated voltage and checked for
satisfactory operation. Do not attempt to operate this unit if the voltage
is not within the minimum and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit. The
unit must be permanently grounded in accordance with local codes, or in
absence of local codes, with N.E.C ANSI/ NFPA NO. 70-1984 or latest edi-
tion by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes permit.
CONTACTOR
R
W
G
G
RW
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
24 VOLT CONTROL WIRING
See
*NOTE
*NOTE:
LOW VOLTAGE CONNECTORS do not apply to heat pumps with
electric heat. LOW VOLTAGE CONNECTORS apply ONLY to DP14C units with
electric heat.
CONTACTOR
R
W
G
G
RW
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
24 VOLT CONTROL WIRING
L3 CONNECTION - 3 PHASE ONLY
See
*NOTE
*NOTE:
LOW VOLTAGE CONNECTORS do not apply to heat pumps with
electric heat. LOW VOLTAGE CONNECTORS apply ONLY to DP14C units with
electric heat.
IMPORTANT NOTE: Some single phase units are equipped with a single-
pole contactor. Exercise caution when servicing as only one leg of the
power supply is broken with the contactor.
To wire the unit, make the following high and low voltage connections.