Service Manual

Field Settings from Outdoor Unit SiUS281811E
138 Part 5 Field Settings and Test Operation
Caution
2. Field Settings from Outdoor Unit
2.1 Capacity Setting
Be sure to carry out capacity setting after changing the main PCB (A1P) to spare PCB.
(for RZR30/36/42/48TAVJU and RZQ30/36/42/48TAVJU only)
Attach the capacity setting adaptor corresponding to capacity class to connector X51A.
Capacity setting is not required for RZR18/24TAVJU and RZQ18/24TAVJU.
Model Adaptor type
RZR30/36/42/48TAVJU
RZQ30/36/42/48TAVJU
J56
X51A