Service Manual

Troubleshooting by Error Codes SiUS281811E
194 Part 6 Service Diagnosis
Troubleshooting
YES
YES
The fan
motor connectors (X1A and
X2A) of the fan PCB (A2P)
are disconnected.
YES
NO
Remove the foreign matter.
NO
YES
NO
NO
YES
NO
NO
YES
CHECK 16
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases.
Replace the fan PCB (A2P).
Turn off the power and wait for
10 minutes.
There is a
foreign matter around
the fan.
Connect the connector
properly.
Replace the indoor fan
motor.
Replace the indoor fan
motor.
Connect the connector
properly.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
The connectors
between the indoor unit
PCB (A1P) and the fan
PCB (A2P) are
disconnected.
The fuse (F3U, white)
on the fan PCB (A2P)
has no continuity.
The fan
can be moved lightly
by hand after the fan motor
connector of the fan PCB
(A2P) is removed.
The
resistance between
the power wire terminals of
the fan motor and motor frame
(metal part) is 1 M: or
below.
Go to the next page.