Service Manual
Table Of Contents
SiUS281811E Field Setting from Remote Controller
Part 5 Field Settings and Test Operation 133
1.5.25 Optional Kit Setting (UV lamp + Humidifier + Economizer)
1.5.26 Residential Dry
1.5.27 Drain Pump Operation Settings
FBQ-P
The drain pump operation can be disabled for natural drainage by changing the following field
setting.
: Factory setting
1.5.28 Humidification when Heating Thermostat is OFF
Setting to Equipped turns ON the humidifier if suction air temperature is 20ºC (68ºF) or more and
turns OFF the humidifier if suction air temperature is 18ºC (64.4ºF) or below when the heating
thermostat is OFF.
: Factory setting
FTQ-TA : Factory setting
Mode No. First Code No.
Second Code
No.
Contents
UV lamp + humidifier fan
speed
Economizer setting for
Mech standby duration
(minutes)
14 (24) 4
01 Refer to controller 10
02 High 10
03 Refer to controller 20
04 High 20
05 Refer to controller 30
06 High 30
07 Refer to controller 40
08 High 40
09 Refer to controller 50
10 High 50
11 Refer to controller 60
12 High 60
13 Refer to controller Free cooling only
14
High Free cooling only
FTQ-TA : Factory setting
Mode No. First Code No. Second Code No. Contents
14 (24) 5
01
Set temperature: room temperature
02
Set temperature: same as cooling set
temperature
Mode No. First Code No. Second Code No. Contents
15 (25) 0
01 —
02
ON
03 OFF
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25) 1
01 Not equipped
02 Equipped