Service Manual
Table Of Contents
Troubleshooting by Error Codes SiUS281811E
188 Part 6 Service Diagnosis
4.7 Drain Level Control System (S1L) Abnormality
Error Code A3
Applicable
Models
FCQ-TA, FBQ-P
Method of Error
Detection
By float switch OFF detection
Error Decision
Conditions
When the float switch goes OFF when conditions for rise of water level are not met
Supposed
Causes
Defective drain pump
Improper drain piping work
Drain piping clogging
Defective float switch
Defective indoor unit PCB
Defective short circuit connector on PCB