Service Manual
Table Of Contents
SiUS281811E Field Setting from Remote Controller
Part 5 Field Settings and Test Operation 119
12 (22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Refer to the page on the right for details. 129
1
External ON/OFF input
(Set when ON/OFF is to be
controlled from outside.)
Refer to the page on the right for details. 129
2
Thermostat differential
changeover (Set when remote
sensor is to be used.)
1°C (1.8°F)
0.5°C (0.9°F) — — 129
3 (7)
Airflow setting when heating
thermostat is OFF
LL tap
Set fan speed OFF — 129
4 Automatic mode differential Refer to the page on the right for details. 130
5
Auto restart after power failure
reset
Not equipped Equipped
— — 130
6 (7)
Airflow setting when cooling
thermostat is OFF
LL tap Set fan speed
OFF — 130
13 (23)
0
Ceiling height setting/setting of
normal airflow
Standard High ceiling (1)
High ceiling
(2)
— 131
1
Airflow direction setting
(Set when a sealing material kit
has been installed)
F (4
directions)
T (3 directions)
W (2
directions)
— 131
2 (6)
Swing pattern settings All direction
synchronized
swing
—
Facing
swing
— 132
4
Airflow direction adjustment
range Draft prevention Standard
Ceiling
Soiling
prevention
— 132
6
External static pressure
settings
Refer to the page on the right for details. 132
14
(24)
4 (8)
Optional kit setting (UV lamp +
humidifier + economizer)
Refer to the page on the right for details. 133
5 (8)
Residential dry Set
temperature:
room
temperature
Set temperature:
same as cooling
set temperature
— — 133
15 (25)
0 Drain pump operation settings — ON
OFF — 133
1
Humidification when heating
thermostat is OFF
Not equipped
Equipped — — 133
2 (5)
Direct duct connection
(when the indoor unit and
energy recovery ventilator are
connected by duct directly.)
Not equipped
Equipped — — 134
3
Drain pump and humidifier
interlock selection
Not
interlocked
Interlocked — — 134
5 Individual ventilation setting — (Normal)
Individual — — 134
1b
4
Display of error codes on the
remote controller
— Two-digit display —
Four-digit
display
134
12
Key-lock pattern settings
No operation
allowed
(Cancel
procedure is
displayed.)
No operation
allowed (Cancel
procedure is not
displayed.)
No menu
operation is
allowed
(Cancel
procedure is
displayed.)
No menu
operation is
allowed any
time.
135
14
Setting restricted/permitted of
airflow block
Refer to the page on the right for details. 135
1c
0
Room temperature display Room
temperature is
not displayed
Room
temperature is
displayed
— — 135
1
Thermistor sensor for auto
changeover and setback
control by the remote controller
Utilize the return
air thermistor
Utilize the
remote
controller
thermistor
— — 135
3 Access permission level setting Level 2
Level 3 — — 136
1e 2 Setback availability N/A
Heat only Cool only Cool/heat 136
Mode
No.
(2)
First
Code
No.
Description
Second Code No.
Page
Reference
01 02 03 04