Service Manual
Table Of Contents
SiUS281811E Troubleshooting by Error Codes
Part 6 Service Diagnosis 217
Troubleshooting
Diagnosis procedure 2
Infrared floor sensor error
(Error code CE-02)
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to sensor
and address data No. 26.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared floor
sensor PCB (A3P) and
the connector
X2A on A2P
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
"--" by the above
verification method.
Normal.
NO
Displays CE-02
again or "--" for
sensor and
address data.
Replace the sensor.