Service Manual

Troubleshooting by Error Codes SiUS281811E
218 Part 6 Service Diagnosis
Troubleshooting
Diagnosis procedure 3
Infrared floor sensor error
(Error code CE-03)
NO
YES
YES
NO
YES
YES
NO
NO
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to
sensor and address data No. 26.
Is the
connection
of the connector
on infrared floor
sensor PCB (A3P) and
the connector
X2A on A2P
normal?
Is the
connection of the
sensor connector
normal?
Displays
"--" by the above
verification method.
Displays
CE-03 again or "--"
for sensor and address
data.
Replace the sensor.
Connect the connector correctly.
Connect the connector correctly.
Normal.
Normal.