Service Manual
Table Of Contents
SiUS121502E Function of CTXS, FTXS, CDXS, FDXS, FVXS Series
Function and Control 43
1.8 NIGHT SET Mode
Outline When the OFF TIMER is set, NIGHT SET Mode is automatically activated. NIGHT SET Mode
keeps the airflow rate setting.
Detail NIGHT SET Mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in cooling, or lowers it slightly in heating. This
prevents excessive cooling or heating to ensure comfortable sleeping conditions, and also
conserves electricity.
<Cooling>
<Heating>
1.9 ECONO Operation
Outline ECONO operation reduces the maximum operating current and the power consumption. This
operation is particularly convenient for energy-saving. It is also a major bonus when breaker
capacity does not allow the use of multiple electrical devices and air conditioners.
It can be easily activated by pushing the ECONO button on the wireless remote controller.
Detail
When this function is activated, the maximum capacity also decreases.
The remote controller can send the ECONO command when the unit is in cooling, heating, dry,
or automatic operation. This function can only be set when the unit is running. Press the ON/OFF
button on the remote controller to cancel the function.
This function and POWERFUL operation cannot be used at the same time. The latest command
has the priority.
(R21924)
TIMER operation
NIGHT SET Mode ON
Target temperature
+0.5˚C (+0.9˚F)
temperature shift
Operation stops
at the set hours
0.5˚C (0.9˚F)
1 hour
TIMER operation
NIGHT SET Mode ON
Target temperature
–2˚C (–3.6˚F)
temperature shift
1 hour
2˚C (3.6˚F)
(R21925)
ECONO operation
(R22012)
Normal operation
Maximum during normal operation
Maximum during ECONO operation
Time
Power
consumption
and current