MXS Service Manual

SiUS121736EA Field Settings
Trial Operation and Field Settings 240
5.3.2 Overview of the Field Settings for FFQ Series
: factory setting
Note: Any function that is not available on the indoor unit is not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01 02 03 04 05 06
10
(20)
0
Filter cleaning
sign interval
Longlife
filter
Light
Approx.
2,500
hrs.
Heavy
Approx.
1,250
hrs.
————
2 Remote controller thermistor Enabled
Disabled————
3 Filter cleaning sign DisplayNo display————
12
(22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Compressor
Operation
output
Error output
Outdoor air
intake
Presence
sensor
13
(23)
0
High air outlet velocity (for high
ceiling applications)
2.7 m
( 8-7/8 ft)
2.7 ~ 3.0 m
(8-7/8~9-13/16 ft)
3.0 ~ 3.5 m
(9-13/16~11-1/2 ft)
———
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow 3-way flow 2-way flow
4 Airflow direction range setting Upper
Normal Lower
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped