MXS Installation Manual

3 English
Accessories
Accessories supplied with the outdoor unit:
A
Installation manual
1
B
Drain socket
It is on the bottom packing case.
1
C
Draincap(1)
6
D
Draincap(2)
3
E
Reducer assy
1
Precautions for Selecting the Location
1)Chooseaplacesolidenoughtobeartheweightandvibrationoftheunit,wheretheoperatingsoundwillnotbeamplied.
2)Choose a location where the hot air discharged from the unit or the operating sound will not cause a nuisance to the
neighbors of the user.
3)Avoid places near a bedroom and the like, so that the operating sound will cause no trouble.
4)Theremustbesufcientspacesforcarryingtheunitintoandoutofthesite.
5)Theremustbesufcientspaceforairpassageandnoobstructionsaroundtheairinletandtheairoutlet.
6)Thesitemustbefreefromthepossibilityofammablegasleakageinanearbyplace.
7)Installunits,powercords,andinter-unitwiresatleast10ft(3m)fromtelevisionandradiosets.(Thisistopreventinterference
toimagesandsounds.Noisemaybeexperiencedeveniftheyaremorethan10ft(3m)awaydependingonradiowave
conditions.)
8)In coastal areas or other places with salty atmosphere or one containing sulphate gas, corrosion may shorten the life of the
air conditioner.
9)Sincewaterwillowfromthedrainoftheoutdoorunit,donotplaceundertheunitanythingwhichmustbekeptawayfrom
moisture.
NOTE
Cannot be installed suspended from ceiling or stacked.
CAUTION
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
• To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
• Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
• To prevent exposure to wind, it is recommended to install a
bafeplateontheairdischargesideoftheoutdoorunit.
• In heavy snowfall areas, select an installation site where the
snow will not affect the unit.
•Construct a large canopy.
•Construct a pedestal.
Install the unit high enough off
the ground to prevent burying
in snow.
01_EN_3P379970-4.indd 3 11/4/2014 2:50:06 PM