Service Manual

Service Diagnosis SiUS121827E
154 Part 6 Service Diagnosis
3.2.2 Method 2
1. Press the center of Temp button and Mode button at the same time.
5C is displayed on the LCD.
2. Select 5C (service check) with Temp or Temp button.
3. Press Mode button to enter the service check mode.
The left-side number blinks.
4. Press Temp or Temp button and change the number until you hear the two consecutive
beeps or the long beep.
5. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the right-
side number does not.
(R24046)
(R11821)
(R24047)
(R11670)
(R24048)