Specifications
AWG
#
142.5mm
2
M4
2.0mm
2
M5
X1M
AKZ 149,329,439,569
(2)Warning output chart
Warning statusNon-warning status
OFF
ON
66 −67
(1)Alarm/operation status output chart
Remote operation (between 【10】 and 【11】)
OFFON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
61−6 2
60−64
60−63
60−61
Warning output (NO contact)
4
1
2
3
AWG
#
124.0mm
2
M5
3.5mm
2
(1)(2)
L1 L3L2
L1 L3L2
(3)
048:
047:
415
480
415
480
415
480440V 460 440 460 440 460
380V 400 380 400 380 400
WVU
MR52Pa
MR30X
MR30W
(X2M)
63646566679101112133031 606162
MR30Y
M5
X1M
AKZ 909
9
AKZ
SERIES
24
Supporting
information
Supporting information
Electric wiring connection instruction diagram
Electric wiring connection instruction diagram
(1)
(2)
(3)
In the case of the standard type and semi-standard type
(−C,−H ,−T ,−046), connect the line to X1M.
In the case of “with breaker” (−B) specifications,
connect to the circuit breaker.
In the case of the semi-standard type (with transformer:−047,−048),
connect the line to the terminal block supplied with the transformer.
Breaker
Terminal
block
Interior of oil cooling unit
Warning
output
Breaker
Power supply capacity … Refer to the max. power consumption and max. consumption
current of the specification sheet of each type.
Connection to power supply terminal block (X1M, Tr)
1. Screw terminal and wiring diameter
1. Straight crimp terminal and wiring diameter
2. Use a round crimp-style terminal for connection.
3. The terminal block is for three poles and the earth wire is
to be secured on the enclosure with a screw
Connect the lines to the terminals corresponding to the main power supply.
(Earth)
or more
or moreor more
or moreor moreor more
Wiring diameter
UL cableIEC cableJIS cable
Screw
terminal
Series
Connection to signal terminal block (X2M)
Normal
Pump
operation
Unassigned (Do not connect to this terminal) Unassigned (Do not connect to this terminal)
Remote
control
For connection
of machine
synchronization
thermistor
For connection of
optional protection
equipment (OP)
Error / Power failure
Alarm level output
(OFF: Level 1, ON: Level 2)
*
Wiring diameter
AWG
#
22∼
#
16
UL cable
0.3mm
2
∼1.5mm
2
IEC cable
0.25mm
2
∼1.25mm
2
JIS cable
Straight pin
terminals
Signal output time chart
Level 1
error or
Lock
Level 2
error
Power failure
(Power OFF)
Normal
Level 2
error
Power failure
(Power OFF)
Normal
Level 1
error or
Lock
Level 1
error or
Lock
Level 2
error
Power failure
(Power OFF)
Normal
Level 2
error
Power failure
(Power OFF)
Normal
Level 1
error or
Lock
Pump operation (NO contact)
Error level (NO contact)
Error / Stop (Power OFF) (NC contact)
Signal output
Operation status
Signal output
Operation status
Normal (NO contact)
1.
Always install an all-pole (3-pole) circuit breaker (to be prepared
by you) of the specified capacity on the main power supply.
*All contact distances must be at least 3 mm.
2. Always ground the unit. Since a noise filter is installed, there
is a risk of electrical shock without proper grounding.
3.
Before opening the electric component box, always turn off the power,
and wait for 5 minutes until internal high voltage has been discharged.
4. Do not energize the equipment with the electric component
box kept open.
DANGER
1. To avoid the effects of noise, connect the power wire by
cutting it to the proper length so that no excess wire comes
into contact with the control board or others.
2. To perform remote control, remove the short-circuit wire
between [10] and [11] and install an operation switch (to be
prepared by you).
3. The mode is set to “Lock mode (Stop mode)” by default.
Before starting operation, follow the procedure to release the
Lock mode from the operation panel. Refer to the operation
manual for the unlocking procedure.
4. The unit is provided with a misoperation prevention switch
(PROTECT) to reject setting from the operation panel.
If you want to use this function, make the necessary setting
referring to the operation manual.
CAUTION
1. The following electric wires can be used on the
terminal block for straight crimp-style terminals.
Single wire: φ0.57∼φ1.44(AWG#22∼#16 )
Stranded wire: 0.25mm
2
∼1.25mm
2
(AWG#22∼16)
2.
Load applicable to [60 - 64] and [66 - 67] is as follows:
Min. applicable load: 10mV DC, 10μA or more
Max. applicable load: 30V DC, 2A (Resistance load)
3. For [10] to [13], please prepare contacts to meet
the condition of minimum applicable load 12V DC
and 5mA.
4. When the length of the thermistor to be connected
to [30] − [31] is longer than 10m, or the wiring is
routed in a poor noise environment, use shielded
wire.
CAUTION
2. Use a straight crimp-style terminal for connection.
3. Use stranded wires for electric connection.
4.
The wiring size is 0.5 mm
2
to 1.5 mm
2
in the case of duplex cable according
to IEC. If using stripped wire, make the stripped length 9 mm to 10 mm.
*Recommended models and manufacturers:
TGN TC−1.25−9T (NICHIFU Co., Ltd.)
APA−1.25N (DAIDO SOLDERLESS TERMINAL MFG. CO., LTD.)