Service manual

ESIE09-08A Troubleshooting by Indication on the Remote Controller
Troubleshooting 185
3.34 “JA Indoor Unit: Malfunction of High Pressure Sensor
Remote Control
Display
JA
Subcode 16
Applicable Models All indoor units
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision Conditions
When the high pressure sensor is short circuit or open circuit.
Supposed Causes Defect of high pressure sensor
Connection of low pressure sensor with wrong connection
Defect of indoor unit PC board (A4P)
Troubleshooting
1: Voltage measurement point
2: Refer to “Pressure Sensor”, pressure / voltage characteristics table on P254.
(V2806)
Be sure to turn off power switch before connecting or disconnecting
connector, otherwise parts may be damaged
Caution
Replace the high pressure sensor.
NO
NO
Replace indoor unit PC board
(A4P).
YE S
YES
Bad wire connection
Value < 0.1 bar
over 60 seconds
Value > 43 bar
over 60 seconds
Faulty sensor
Connect the high pressure sensor
and turn on again.
The high
pressure sensor is
connected to X17A of
indoor unit PC
board (A4P).
Indoor unit PC board A4P
+5V
X17A
Red
Black
White
GND
*2 Measure DC voltage here.
High pressure sensor
4
3
2
1
(V2807)
Microcomputer
A/D input