Service manual

ESIE09-08A Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 287
Differences
Change in pressure
Change in service port diameter
7. Charge hose for R-410A
Specifications
Working pressure 5.08 MPa (51.8 kg/cm
2
)
Rupture pressure 25.4 MPa (259 kg/cm
2
)
Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
The cylinder can not be used for mixed refrigerant since mixing ratio is changed during charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is generated
inside charging cylinder.
9. Weigher for refrigerant charge
Specifications
High accuracy
(Hose with ball valve)
Can not be used