Service manual

SiBE05-722_C Field Settings
Trial Operation and Field Settings 113
4.2 Facility Setting Jumper (cooling at low outdoor
temperature)
Outline This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail You can expand the operation range to –15°C by cutting the jumper on the outdoor unit PCB. If
the outdoor temperature falls to –20°C or lower, the operation stops. If the outdoor temperature
rises, the operation starts again.