Service manual

Control Specification SiBE05-722_C
46 Function and Control
3.10 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish.
Detail Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes of accumulated time pass after the start of the operation, or ending the
previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature. (B°C)
: The same value continues.
RXS25/35E2V1B
RXS25/35G2V1B
RXS25/35G2V1B9
RXS25/35J2V1B
RXS25K3V1B RXS35K2V1B
A (minutes)28282828
B (°C) 4 ~ 18 4 ~ 18 4 ~ 18 4 ~ 18
C (Hz) 74 76 68 76
D (Hz) 86 86 86 86
E (seconds) 50 50 50 50
F (seconds) 60 60 60 60
G (seconds) 480 480 480 480
H (seconds)50605060
J (pulse) 450 450 450 450
K (pulse) 350 350 350 200
L (pulse) 350 350 400 300
M (pulse) 450 450 450 450
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz 0 Hz
C Hz
D Hz
5 sec.
K pulse
M pulseJ pulse
Initial opening
PI control
5 sec.
H sec.
(R18152)
Electronic expansion
valve opening
E sec.
F sec.
G sec.
L pulse