Specifications
SiBE05-722_A Field Settings
Trial Operation and Field Settings 209
2. Field Settings
2.1 When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, 1 of the 2 pairs of indoor unit and wireless remote
controller can be set for different address.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB
Cut the address setting jumper JA on the control PCB.
Wireless Remote
Controller
Cut the address setting jumper J4.
ADDRESS JA
EXIST 1
CUT 2
(R12419)
Address
J4
EXIST
CUT
1
2
J4
(R6573)