Specifications
6L86 3URWHFWLRQ&RQWURO
)XQFWLRQ
3URWHFWLRQ&RQWURO
+LJK3UHVVXUH3URWHFWLRQ&RQWURO
7KLVKLJKSUHVVXUHSURWHFWLRQFRQWUROLVXVHGWRSUHYHQWWKHDFWLYDWLRQRISURWHFWLRQGHYLFHVGXH
WRDEQRUPDOLQFUHDVHRIKLJKSUHVVXUHDQGWRSURWHFWFRPSUHVVRUVDJDLQVWWKHWUDQVLHQW
LQFUHDVHRIKLJKSUHVVXUH
>,QFRROLQJRSHUDWLRQ@
>,QKHDWLQJRSHUDWLRQ@
Pc
>
500 psiEvery 10 sec.
Pc
>
493 psi
Pc
<
479 psi
Pc>3.6MPa
Keeping the current step
Every 60 sec.
479 psi≤Pc≤493 psi
Every
5 min.
or
&
High pressure not limited
High pressure limited
INV upper limit frequency:
1-step up from current
compressor frequency
INV upper limit frequency:
1-step up from current
compressor frequency
Pc: HP pressure sensor detection value
INV upper limit frequency :
1-step down from current
compressor frequency
When occurring 3 times within 30
minutes, HPS is activated without high
pressure standby, thus outputting the
malfunction code "E3".
High pressure
standby
(V3173)
• INV upper limit frequency
• Pc ≤ 493 psi
• During oil return operation
• After oil return operation
• Stopping operation
• Heating operation
Pc
>
479 psi
Pc
>
522 psi
52Hz
Pc
<
450 psi
High pressure not limited
High pressure
limited
High-pressure drop
Pc: HP pressure sensor detection value
When HPS is activated, the
malfunction code "E3" is output.
High pressure
standby
(V3174)