7.8 Checking procedure of error record
7.9 Registration method of the service contract
3P243521-1
20 English
Registration method of the service 9.
contract
Registration of the service contract. Ɣ
9-1
Press and hold Cancel button for
4 seconds or longer in the basic
screen.
Field setting menu is displayed.
Select
9-2
Register Service Contract in
the fi eld setting menu, and press
Menu/Enter button. “Register service
contract” menu screen is displayed.
Select
9-3
Register Service Contract ,
and press Menu/Enter button.
Enter the telephone number.
9-4
Numeric varies by using (Up/
Down) button. Enter from the left end,
and blank digit should be left as “ - ”.
Press Menu/Enter button.
9-5
Setting confi rmation screen is
displayed.
Select
9-6
Yes and press Menu/Enter
button.
Setting details are determined and fi eld
setting menu screen returns.
Press Cancel button once.
9-7
The basic screen returns.
19- <Basic screen>
<Field setting menu screen>
29-
Return Setting
Field setting
Test operation ON/OFF
Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set
1/2
Press Menu/Enter button.
39-
Return Setting
Register Service Contract
None
Register Service Contract
Press Menu/Enter button.
49-
Return Setting
Register Service Contract
Register Service Contract
–––––––––––––––
1/2
59-
Return Setting
Register Service Contract
Register Service Contract
0123
456
7890
–––
1/2
Press Menu/Enter button.
<Setting confi rmation screen>
69-
Return Setting
Is it settled by setting?
Register Service Contract
Yes No
Press Menu/Enter button.
<Field setting menu screen>
01_EN_3P243521-1.indd 20 2/3/2009 1:19:25 PM
English 19
Remote controller display Description
No display
Power outage, power voltage error or open-phase Ɣ
Wrong wiring (between indoor and outdoor units) Ɣ
Indoor PC-board assembly failure Ɣ
Remote controller wiring disconnection Ɣ
Remote controller failure Ɣ
Fuse blow (outdoor unit) Ɣ
Display of
“Connection under check
Please wait for a moment” is turned on.
Indoor PC-board assembly failure Ɣ
Wrong wiring (between indoor and outdoor units) Ɣ
Though
“Connection under check
Please wait for a moment” is displayed for 90 seconds at maximum after power-on, this does not mean a
failure. (Determine after 90 seconds.)
Checking procedure of error record8.
8-1
Press and hold Cancel button for
4 seconds or longer in the basic
screen. Field setting menu is dis-
played.
Select
8-2
Error record in the fi eld setting
menu, and press Menu/Enter button.
The error record menu screen is
displayed.
Select
8-3
Remote controller record in the
error record menu, and press Menu/
Enter button.
Error codes and unit No. can be
confi rmed in the error record display
screen.
In the error record, 10 items from the
8-4
latest are displayed in order.
Press Cancel button in the error record
8-5
display screen 3 times.
The basic screen returns.
18- <Basic screen>
<Field setting menu screen>
28-
Return Setting
Field setting
Error record
Indoor status display
Outdoor status display
Fan forced operation ON
Main/Sub changeover
Filter element sign OFF
2/2
Press Menu/Enter button.
38-
Return Setting
Error record
Remote controller record
Indoor unit record
2/2
Press Menu/Enter button.
48-
58-
Return Setting
Remote controller record
Unit Error Date Time
01
–– –– ––
/
––
/
–– ––:––
02
–– –– ––
/
––
/
–– ––:––
03
–– –– ––
/
––
/
–– ––:––
04
–– –– ––
/
––
/
–– ––:––
1/3
Unit No.
Latest record
01_EN_3P243521-1.indd 19 2/3/2009 1:19:24 PM