Specifications

Si38-606 Field Setting
Test Operation 81
Auto restart after power failure reset
For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
or the main power supply is turned on again after once turned off. However, for the air
conditioners with the setting, the units may start automatically after power failure reset or the
main power supply turned on again ( return to the same operation condition as that of before
power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
Air Flow Adjustment - Ceiling height
Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
In the Case of FXA, FXH
In the Case of FXF25~80
In the Case of FXF100~125
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Mode No.
Setting Switch
No.
Setting Position
No.
Setting
13(23) 0
01 Wall-mounted type: Standard
02 Wall-mounted type: Slight increase
03 Wall-mounted type: Normal increase
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets 3-way Outlets 2-way Outlets
13 (23) 0
01 Standard (N) Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
02 High Ceiling (H) Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
03 Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets 3-way Outlets 2-way Outlets
13 (23) 0
01 Standard (N) Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
02 High Ceiling (H) Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
03 Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m