BRC1H71W Installation Manual

English 27
NOTICE
Installation of optional accessories on the indoor unit may require changes to eld settings.
See the manual of the optional accessory.
For eld setting details related to the indoor unit, see installation manual shipped with the indoor
unit.
Field setting mode list
Mode
No.
(Note 1)
First
Code
No.
Description
Second Code No. (Note 2)
(Items in bold are factory default settings)
01 02 03 04
10 (20)
2
Priority of thermistor
sensors for space
temperature control
The return air
thermistor is
primary and
the remote
controller
thermistor is
secondary.
The remote
controller
thermistor is
not utilized.
Only the return
air thermistor
will be utilized.
Only the
remote
controller
thermistor
will be
utilized.
5
Room temperature
value reported to
multizone controllers
Return air
thermistor
Thermistor
designated by
10-2 above
(Note 3)
12 (22) 2
Thermo-on/off
deadband
(Note 4)
2°F (1°C) 1°F (0.5°C)
1C 01
Change room
temperature display
Inlet
temperature
Remote
controller
thermistor
1E 02 Setback availability
N/A
Heat only Cool only Cool/Heat
Notes) 1. Field settings are normally applied to the entire remote control group, however if
individual indoor units in the remote control group require specic settings or for
conrmation that settings have been established, utilize the mode number in
parenthesis.
2. Any features not supported by the connected indoor unit will not be displayed.
3. When mode 10-2-01 is selected, only the return air temperature value is reported
to the multizone controller.
4. The actual default deadband value will depend upon the indoor unit model.