MXS Service Manual

SiUS121736EA SA Indoor Unit Functions
Functions and Control 88
3. Auto-off by sensor (with presence sensor)
After pre-determined time has elapsed without detection of human presence, the unit automatically
stops operation.
The auto-off time can be set between 1- 24 hours by the hour.
Once the unit stops operation by auto-off function, the system would not restart even if the human
is detected again.
Auto-off by sensor is enabled only when decoration panel BYFQ60C2W1W(S), sensor kit
BRYQ60A2W(S) and wired remote controller BRC1E73 are connected to the main unit and
auto-off by sensor is set to “enabled” on the wired remote controller.
Factory setting is “disabled”.
Setting on the remote controller
4. Room temperature adjustment by sensing (with floor sensor)
The system uses living space temperature calculated from temperatures detected by room
temperature thermistor (suction air thermistor in the indoor unit) and floor sensor, as the target
temperature.
Operation becomes more optimized by using not only suction air temperature but floor temperature.
This function is enabled when decoration panel BYFQ60C2WAW(S) and sensor kit
BRYQ60A2W(S) is connected to the main unit.
2
3
4
1
Press buttons to select
Auto-off by Sensor .
Press Menu/OK button to display
Auto-off by Sensor menu.
Press buttons to select Enable .
Press buttons to go into the auto-off
time setting.
Press buttons to set auto-off hour(s)
(1 ~ 24).
Press Menu/OK button. Then the
confirmation screen is displayed.
Press Cancel button for 4 seconds on
the basic screen to display Service
Settings menu.
Press buttons to select Energy
Saving Options .
Press Menu/OK button to display
Energy Saving Options menu.
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
Energy Saving Options
Setpoint Range Limitation
Auto-setback by Sensor
Auto-off by Sensor
5
Setting
Auto-off by Sensor
Enable/Disable: Enable
Auto-off in: 24 hr(s)
Setting
Auto-off by Sensor
Enable/Disable: Enable
Auto-off in: 24 hr(s)
Setting
Save the settings?
Auto-off by Sensor
Yes No
Press buttons to select Yes .
Press Menu/OK button to confirm the
settings and to return to the Service
Settings menu.