How to use reducer
Use the reducers supplied with the unit as described below.
1) Connecting a pipe of φ1/2 (φ12.7) to a gas pipe connection port for φ5/8 (φ15.9):
2) Connecting a pipe of φ3/8 (φ9.5) to a gas pipe connection port for φ5/8 (φ15.9):
3) Connecting a pipe of φ1/4 (φ6.4) to a liquid pipe connection port for φ3/8 (φ9.5):
When using the reducer packing shown above, be careful not to overtighten the nut. (See <Table-1>.)
Apply refrigeration oil on the connection port where the flare nut is fitted.
Gasket (1)
No.1
f
5/8 (
f
15.9)
®f
1/2 (
f
12.7)
No.2
f
3/8 (
f
9.5)
®f
1/4 (
f
6.4)
No.3
f
5/8 (
f
15.9)
®f
1/2 (
f
12.7)
No.5
f
5/8 (
f
15.9)
®f
3/8 (
f
9.5)
No.6
f
5/8 (
f
15.9)
®f
3/8 (
f
9.5)
No.4
f
3/8 (
f
9.5)
®f
1/4 (
f
6.4)
Gasket (2) Reduce and gasket
Connection port of outdoor unit
No. 1
Be sure to attach
the gasket.
No. 3
Flare nut (for
B
5/8 (
B
15.9))
Inter-unit pipe (
B
1/2 (
B
12.7))
Flare nut (for
B
3/8 (
B
9.5))
Inter-unit pipe (
B
3/8 (
B
9.5))
No. 5
No. 6
Be sure to attach the gasket.
Inter-unit pipe (
B
1/4 (
B
6.4))
Flare nut (for
B
3/8 (
B
9.5))
Be sure to attach the gasket.
No. 2
No. 4
unit: inch (mm)