3MXL24RMVJUA Installation Manual

8English
Outdoor Unit Installation
1. Installing the outdoor unit
1) When installing the outdoor unit, refer to “Precautions for Selecting a Location on page 3 and the Outdoor Unit
Installation Diagram on page 4.
2) If drain work is necessary, follow the procedures below.
2. Drain work
CAUTION
In cold areas, do not use a drain socket, drain caps (1,2)
and a drain hose with the outdoor unit. (Drain water may
freeze, impairing heating performance.)
• Ifthedrainportiscoveredbyamountingbaseoroor
surface, place additional foot bases of at least 1-1/4
inch (30mm) in height under the outdoor unit’s feet.
1) Attach
C
drain cap (1) and
D
drain cap (2).
2) Attach
B
drain socket.
• When attaching
B
drain socket to the bottom
frame, make sure to connect the drain hose to the
drainsocketrst.
3. Refrigerant piping
CAUTION
• Usethearenutxedtothemainunit.(Thisistopreventthearenutfromcrackingasaresultofdeteriorationovertime.)
• Topreventgasleakage,applyrefrigerationoilonlytotheinnersurfaceoftheare.(UserefrigerationoilforR410A.)
• Useatorquewrenchwhentighteningthearenutstopreventdamagetothearenutsandgasleakage.
• Alignthecentersofbotharesandtightenthearenuts3or4turnsbyhand,thentightenthemfullywithaspanneranda
torque wrench.
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration
oil only to the inner
surface of the flare.
Do not apply refrigeration oil to
the flare nut to avoid tightening
with excessive torque.
Apply oil
Torque wrench
Piping union
Flare nut
Spanner
Tighten
Flare nut tightening torque
φ1/4 inch (6.4mm)
φ3/8 inch (9.5mm)
φ1/2 inch (12.7mm)
φ5/8 inch (15.9mm)
10-1/2 – 12-3/4ft • lbf (14.2-17.2N • m)
24-1/8 – 29-1/2ft • Ibf (32.7-39.9N • m)
36-1/2 – 44-1/2ft • lbf (49.5-60.3N • m)
45-5/8 – 55-5/8ft • lbf (61.8-75.4N • m)
Width across flats
Valve cap tightening torque
Service port cap tightening torque
8 10-7/8ft • lbf
(10.8-14.7N • m)
11/16 inch (17mm)
10-1/2 12-5/8ft • lbf
(14.2-17.2N • m)
3/4 inch (19mm)
12-5/8–15-3/8ft • lbf
(17.1-20.9N • m)
7/8 inch (22mm)
16–20-1/4ft • lbf
(21.6-27.4N • m)
1-1/16 inch (27mm)
35-3/8 44-1/8ft • lbf
(48-59.8N • m)
Bottom frame
Drain cap
Pinch the bottom
frame in.
Drain cap (1)
Drain cap (2)
D
Drain cap (2)
Air outlet side
B
Drain
socket
C
D
Bottom frame
Drain socket
Hose (available commercially,
inner dia. 5/8 ” (16mm))
B
English