Outdoor Unit Installation
6. Relling refrigerant
Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
R410Aisamixedrefrigerant,soaddingitingasformmaycausetherefrigerantcompositiontochange,preventingnormal
operation.
1) Beforelling,checkwhetherthecylinderhasasiphonattachedornot.(Itshouldhavesomethinglike“liquidllingsiphon
attached” displayed on it.)
Filling a cylinder with an attached siphon
Stand the cylinder upright when filling.
There is a siphon pipe inside, so the
cylinder need not be upside-down to
fill with liquid.
Filling other cylinders
Turn the cylinder upside-down
when filling.
• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
7. Charging with refrigerant
CAUTION
Eventhoughthestopvalveisfullyclosed,therefrigerantmayslowlyleakout;donotleavethearenutremovedforalong
period of time.
• Ifthetotallengthofpipingforallroomsexceedsthegurelistedbelow,additionallychargewith0.21oz/ft(20g/m)of
refrigerant (R410A) for each additional piping length.
Outdoor unit capacity class
Total length of piping for all rooms
5MXS48∗, 4MXL36∗
131-5/8ft (40m)
• If additional refrigerant has been charged list the amount added on the nameplate on the shield cover.