5MXS48TVJU Installation Manual

13 English
Wiring
[Wiring procedure]
1) Strip the insulation from the wire (3/4 inch (20mm)).
2)
Connect the inter-unit wires between the indoor and
outdoor units so that the terminal numbers match.
Tighten the terminal screws securely. It is recommended
that a slot-head screwdriver be used to tighten the screws.
3) Be sure to match the symbols for wiring and piping.
4)
Pull the wire lightly to make sure that it does not
disconnect.
5) After completing the work, reattach the shield cover and
right side plate to their original positions.
• Attach so that the shield cover hooks (2 locations) are
securely engaged.
Outdoor unit
60Hz
208/230V
Room A
To room D
To room B
To room E
Room
C
To room C
Room
D
Room
E
Room
B
Room
A
Indoor unit
power
supply
Follow local codes for wiring and
safety devices between outdoor
unit and power source.
Note: Take care to ensure that all wiring
between indoor unit and outdoor unit has a
consistent connection. Any splices can cause
communication errors.
: The Room A and Room B terminal
blocks, as well as the Room C and Room D
terminal blocks, are actually integrated.
Recommend using AWG14, stranded and insulated wire for connections
between indoor and outdoor units.
Local code always supersedes recommendation.
Shape the wires so that there is
no lifting of the shield cover or
other structural parts.
For Room AFor Room E For Room C For Room D For Room B
For power supply
Ground wires
Ground wires
Use the specified wires and
connect them securely.
Terminal block
CAUTION
Precautions to be taken for power supply wiring
• When using stranded wires, make sure to use the round crimp-style
terminal for connection to the power supply terminal block.
Stranded
wire
Round crimp-style
terminal
Good
Round crimp-
style terminal
Flat washer
Screw
Wrong
Flat washer
Round crimp-
style terminal
Screw
Flat washer
Screw
Round
crimp-style
terminal
A
Arrow view A
• When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead.
Improperworkmaycauseheatandre.
Strip wire end
to this point.
Excessive strip length
may cause electric shock
or current leakage.
Stripping wire at terminal block
Good Wrong
Good Wrong
Ground
This air conditioner must be grounded. For grounding, follow all local, and state electrical codes.