EDUS 391000 - C Controls AMERICAS
EDUS391000-C Controls 1. Control Systems..........................................................................................2 2. Control Devices...........................................................................................3 2.1 2.2 2.3 2.4 2.5 2.6 2.7 BRC1E71 Navigation Remote Controller (Wired Remote Controller) .......... 3 BRC4C / 7C / 7E Wireless Remote Controller / Receiver .......................... 12 BRC2A71 Simplified Remote Controller...........................................
Control Systems EDUS391000-C 1. Control Systems Optional Accessories of Operation Control System Type No.
EDUS391000-C Control Devices 2. Control Devices 2.1 BRC1E71 Navigation Remote Controller (Wired Remote Controller) 2.1.1 Features BRC1E71 · Clear Display............................. Equipped with backlight and large sized character display and buttons. · Stylish........................................ Basic tone is white and arrow keys are located at the center. · Simple Operation ...................... Simple operation used with arrow keys and menu-driven method. · Multilingual Display ............
Control Devices EDUS391000-C Stylish Simple and Functional Design (1) Large text display (2) Large buttons (3) Backlight (4) No-cover design (1) (3) (2) Simple Operation Compared to the conventional structure of button allocation for each function, the number of buttons has been decreased (from 15 to 9). Can intuitively handle frequently performed basic operations.
EDUS391000-C Control Devices Available for simple operation with arrow keys and menu-driven system. Available for simple operation with arrow keys and menu-driven system. Press "Menu/OK" button to change the screen and then the main menu appears. Available for simple operation with arrow keys and menu-driven system. Select the item you wish to set with direction keys and press "Menu/OK" button at the item you wish to set and the setting entry screen appears.
Control Devices EDUS391000-C Available for simple operation with arrow keys and menu-driven system. The item you wish to set can be changed with up or down button. Guide on display The display gives an explanation of each setting for easier operation.
EDUS391000-C Control Devices Multilingual Display Available for display in 3 different languages. Always available for switching display by selecting from main menu.
Control Devices EDUS391000-C Other Features 8 Controls
EDUS391000-C 2.1.
Control Devices 2. 1. 2. EDUS391000-C In the case of centralized remote controller connection. When connecting a centralized related device (*1), the following functions cannot be set. Schedule function and Setback temperature function Auto Changeover function by the remote controller (*1) this means all centralized remote controller.
EDUS391000-C 2.1.4 Control Devices Dimensions Unit (in.) IF THE HOLE SIZE IS TOO LARGE OR THE LOCATION NOT PROPER, THE WIRE MAY COME OUT OF THE HOLE IN THE REMOTE CONTROLLER. 3D065275 2.1.
Control Devices 2.2 EDUS391000-C BRC4C / 7C / 7E Wireless Remote Controller / Receiver BRC7C812 6-3/16 Unit (in.) 2-7/16 11/16 C:3D005912D BRC4C82 6-3/16 4-3/4 Unit (in.
EDUS391000-C Control Devices BRC7E83 Unit (in.) 3D049336 BRC7E818 6-3/16 Unit (in.
Control Devices 2.3 EDUS391000-C BRC2A71 Simplified Remote Controller 2.3.1 Name and Function 6 13 2 1 3 5 H L F 7 4 8 9 11 10 12 BRC2A71 REMOTE CONTROLLER: NAME AND FUNCTION OF EACH SWITCH AND DISPLAY DISPLAY “ CONTROL) ON/OFF BUTTON Press the button and the system will start. Press the button again and the system will stop. OPERATION LAMP (RED) The lamp lights up during operation. Blinks in case of stop due to malfunction.
EDUS391000-C Control Devices 2.3.2 Installation 1. Remove the upper part of remote controller. Insert a minus screwdriver into the slot between the upper and the lower part of remote controller. NOTE 1. Do not directly touch the PC board with your hand. 2. Wire the indoor unit. Connect terminals P1 and P2 on the rear of the lower part of remote controller to terminals P1 and P2 on the indoor unit. (Terminals P1 and P2 have no polarity.) NOTES 1.
Control Devices EDUS391000-C NOTES 2If controlling with one remote controller, be sure to set it to "MAIN." 2Set the remote controller before turning power supply on. " " is displayed for about one minute when the power supply is turned on, and the remote controller cannot be operated in some cases. 5. Reattach the upper part of remote controller. NOTE 1. Do not directly touch the PC board with your hand. 3P146205-2 2.3.3 Dimensions Unit (in.
EDUS391000-C 2.4 Control Devices DCS302C71 Central Remote Controller You can connect up to 64 groups of indoor units (max. 128 units); let’s you operate or monitor ON/OFF, temperature setting, etc., by zone individually or together. Up to 2 units are connectable within 1 system (Up to 4 units in case of the double central control mode) Executes zone control for up to 64 zones and is designed for operation efficiency.
Control Devices EDUS391000-C System Configuration (Group / Zone Control) Group control The group means the indoor units connected by the same control wiring for remote controller (connected to terminal P1 and P2) and all the unit in group have “the same setting” and “the same operation”. The indoor units in the group are controlled by the remote controller for indoor unit. The number of indoor units in one group is up to 16 units.
EDUS391000-C Control Devices System Configuration (Control by 2 central remote controllers) Up to 128 indoor units can be connected in one system. 2 or 4 central remote controllers are required. It is possible to control the same unit from 2 locations. Up to 16 unified ON/OFF controllers can be connected. (8 controllers × 2 locations) One schedule timer can be connected. Notes: 1.Electrical power should be supplied to each central remote controller. (Single phase 100~240V) 2.
Control Devices EDUS391000-C 2.4.2 Specifications / Dimensions Specifications DCS302C71 Power supply voltage / frequency AC100~240V ±10% 50/60Hz Power consumption Max. 8W Setting data backup Non-volatile memory (Data preserved semi-permanently) Effects of instantaneous power failure No effect for 20 mili-sec. or less Forced OFF input Operation on the local side cannot be carried out during forced OFF input.
EDUS391000-C Control Devices 2.4.3 Names and Functions of Operating Part Display part DISPLAY (OPERATION MODE) Displays operating state. DISPLAY(VENTILATION CLEANING DISPLAY) This is displayed when a Ventiair total enthalpy heat exchanger unit or other such unit is connected. DISPLAY (OPERATION MODE) Displays operating state. OPERATION LAMP (RED) Lit while any of the indoor units under control are in operation. UNIFIED OPERATION BUTTON Press to operate all indoor units.
Control Devices EDUS391000-C 2.4.4 Description of Functions Individual Screen, all Screen, Zone Screen This controller can perform operations in the individual screen, all screen, or zone screen. Individual screen The individual screen is used when performing group operations. All screen The all screen is used when performing operations for all units at once. Zone screen The zone screen is used when performing zone operations.
EDUS391000-C Control Devices Cool/heat Selection Eligibility Setting by Remote Controller for Indoor Unit The outdoor unit of can freely be selected the operation mode (fan, dry, auto [Heat Recovery only], cooling or heating) by the remote controller for indoor unit. However, you have to set the selection eligibility for fan, dry, cooling and heating operation on the one of the remote controller out of the indoor units connected to the outdoor unit.
Control Devices EDUS391000-C Description of operation and its function Remote control having the selection eligibility Remote controller having no sign. ( Remote control having the selection eligibility Remote controller having no sign. ( Set to Cooling, Heating and Auto (only for Heat Recovery series); Other remote controller controller having ( Remote ) no sign. ) Set to [Fan]; ) Other remote controller controller having ( Remote ) no sign.
EDUS391000-C Control Devices Sequential Start Each unit operates in sequence. For example, if you set the simultaneous operation by the central remote controller, which controls 1-00 ~ 4-15 and 5-00 ~ 8-15 groups, two outdoor units start simultaneously. Registering Zone It is possible to set multiple groups as one zone and control each zone separately. No zones are registered when the unit is shipped from the factory.
Control Devices EDUS391000-C Batch deletion of zone registration 1. 9 Pressing the "ALL " for at least four seconds while 8 pressing the "FILTER SIGN RESET" button when 2 "ZONE SET" is displayed will delete all zone registrations. The zone registrations for all units will be lost. Zone setting Set the screen of [Zone 0] on the display, and if you set the following mode, you can set to all the registered zone on the central remote controller by one operation.
EDUS391000-C Control Devices Changing the Fan Direction and Fan Strength This changes the fan direction and strength settings in the air conditioner. Changing the fan direction and strength is done in the individual screen. 2 4 INDIVIDUALLY 80 F L 5 1 3 6 [Registration] 1. 1 Press the "ALL/INDIVIDUAL button" to enter the 2 individual screen. The unit will enter the individual screen automatically if nothing is done for one minute. 2.
Control Devices EDUS391000-C [Registration] 1. 1 Pressing the "TIMER No." button causes the number set for timer number 1 to blink. If no timer setting has been made " " will be displayed. Select the desired timer number by pressing the 1 "TIMER NO." button. 1 2 No. No 2. 2 Once the desired timer number is displayed, press the "SET" button. Press the 2 "SET" button within 10 seconds after the timer number is displayed. The display will return to how it was after 10 seconds.
EDUS391000-C Control Devices 2.4.5 Wiring Instructions Wiring instructions For control wiring of DIII-NET, you can select from the following 3 types of wiring methods. 1. Series method : Wiring is connected by a single line from the central controller. 2. Bus method : Up to 16 branches is possible. Never diverge the sub-branches from the branch line. 3. Star method : Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
Control Devices EDUS391000-C 2.4.6 Instructions for Initial Setting Group No. Setting for Central Control Equipment Group No. should be set for each group by the remote controller for indoor unit, when you operate the system with central remote controller and unified ON/OFF controller. (For the same control group, set only one of the unit.) Remote controller for indoor unit 1. Turn ON the power of the indoor unit and central remote controller. (Unless the power is ON, no setting can be made.
EDUS391000-C Control Devices Even in the system without remote control, connect the remote controller once to set group No. for central control equipment and remove the remote controller after setting. When you set the group No., be sure to supply the power to the central remote controller, the unified ON/OFF controller and the indoor unit.
Control Devices EDUS391000-C 2.4.7 Selection of Control Mode No. Select whether to accept or reject operations by local remote controller such as Turning on/off, temperature adjustment and operation mode setting respectively, and decide the control mode No. the right side of the table below.
EDUS391000-C Control Devices Timing Chart for Each Control Mode No. (VRV system) Timing charts for scheduled operation and remote controller control for each control mode No. as follows. 1. Remote controller rejection (Code No. 0, 1, 10, 11) 2. Remote controller off only accepted (Code No. 2, 3, 12, 13) 3. Central priority (Code No.
Control Devices EDUS391000-C 5. Remote controller permission timer (Code No.
EDUS391000-C Control Devices 2.4.8 Setting of Central Remote Controller (Be sure to set 1 ~ 3 before electrical power is supplied.) 1. Connector for setting "Main" for control (Connector is provided when shipped from factory) When only one central remote controller is used, never remove the connector for setting "Main" for control.
Control Devices EDUS391000-C 4. Forced reset switch When changing the setting of the connector for setting main controller, etc., you can reset simply by setting it to the reset side once and returning to the normal side, without turning the power OFF. (For normal operation, set the switch to the normal side) 5. Special Function Settings Special functions on the central control system can be changed while in FIELD SETTING mode. Mode No. No. of Switch Setting C SET 3 1.5 2 4 Setting Procedure 1.
EDUS391000-C Control Devices 6. Refreshed operation Refreshed operation is the function to transmit setting of "Temperature control", "Temperature setting" automatically from DCS302C71. "Refreshed operation" is "ON" when shipped from the factory. Factory Setting It depends on the setting of outdoor systems that an indoor unit setting is "Temperature control " or " Temperature setting".
Control Devices EDUS391000-C Setting Contents and Setting No. Mode No. Setting contents No.
EDUS391000-C Control Devices Installation (1) Open the upper part of remote controller. Insert a – screwdriver (2 locations) into the recess between the upper part and the lower part of remote controller and twist the screwdriver lightly. – screwdriver (2 locations) PC board is attached with both the upper and lower part of remote controller. Do not damage the board with the screwdriver.
Control Devices 2.5 EDUS391000-C DCS301C71 Unified ON/OFF Controller Turns up to 16 groups of indoor units (max. 128 units) on/off (operation/stop) by individual group or all at once, and lets you check display of operation/malfunction at the same time. For a maximum of 16 groups of indoor units (max. 128 units), unified operation/stop or individual operation/stop can be performed with this optional accessory. Also allows you check operation/error display at a glance.
EDUS391000-C Control Devices The groups of indoor units are as follows: 1. One indoor unit without remote controller 2. One indoor unit controlled by one or two remote controllers 3. A maximum of 16 indoor units controlled in groups by one or two remote controllers 2.5.2 Electric Wiring All wiring, components and materials to be procured on the site must comply with the applicable local and national codes. Use copper conductors only.
Control Devices EDUS391000-C 1. Series Wiring 2. Bus Type Wiring (Can be branched up to 16 branches) Example of 3 branches 3. Star Type Wiring (Can be branched up to 16 branches) Example of 3 branches Note: 1. No branching is allowed after branching. 2. Use a relay terminal board (field supplied) to branch more than 3 control wires from the same terminal board.
EDUS391000-C Control Devices Note: Do not connect the power supply wiring to the control terminal strip. If connected by mistake, it may damage or burn electrical parts of optional controllers for centralized control and indoor unit. It may result in serious danger. Be sure to check wirings before turning the power ON. 2.5.3 Dimension Unified ON/OFF Controller DCS301C71 Unit (in.
Control Devices EDUS391000-C 2.5.4 Installation 1. Open the upper part of remote controller. Insert a minus screwdriver (2 locations) into the recess between the upper part and the lower part of remote controller and twist the screwdriver lightly. PC board is attached with both the upper and lower part of remote controller. Do not damage the board with the screwdriver. 2.
EDUS391000-C Control Devices 2. Switch for Setting Each Address (DS1) These switches are used to set group control address. Groups Nos. 1-00 through 1-15 are grouped in the same control group when the unit is shipped from the factory. After setting, attach the number seal applicable to respective control range of the attached switch display sticker, as shown in the diagram below. (Example) In The Case of 1-00 to 1-15, Attach N. 3.
Control Devices EDUS391000-C 5. Control Mode Selector (DS2) The following four patterns of control mode can be set. Control Mode Individual Centralized Timer Operation Possible by Remote Controller ON/OFF Control Impossible by Remote Controller Content After operated by unified ON/OFF controller, operation/stop is freely controlled by remote controller until stopped by unified ON/OFF controller.
EDUS391000-C Control Devices 2.5.6 Setting Group No. for Centralized Control Set the group number of each group of the indoor unit from the remote controller. (In case of no remote controller, also connect the remote controller and set the group No. Then, remove the remote controller.) 1. Turn ON the power of the indoor unit and unified ON/OFF controller. (Unless the power is ON, no setting can be made.) Check that the installation and electrical wiring are correct before turning the power supply ON.
Control Devices 2.6 EDUS391000-C DST301BA61 Schedule Timer Enables you to connect and control weekly schedule for up to 128 indoor units all together. Simultaneous control of up to 128 indoor units is managed by a week schedule. The start and stop time for twice a day can be set for the week in increments of 1 minute. By combining with a central remote controller and schedule timer, you can construct a system that matches the size and use of the building.
EDUS391000-C Control Devices 2.6.2 Names and Functions (DST301BA61) 4 6 5 3 1 2 7 8 DST301BA61 9 10 11 Fig. 1 12 15 14 16 17 DST301BA61 13 18 19 20 Fig.
Control Devices EDUS391000-C UNIFIED OPERATION BUTTON “ 1 Press this button to perform the unified operation regardless of the No. of programmed time. ” The light turns on during the operation of the indoor unit. DISPLAY “ 4 5 CLOCK ADJUSTING BUTTON “ ” (TIME NO.) PROGRAMMING START BUTTON “ DISPLAY “ OFF ” (HOLIDAY SETTING) Lights above the day of the week set as holiday. The operation controlled by timer is not available on that day.
EDUS391000-C Control Devices 2.6.3 Dimension Schedule Timer DST301BA61 Unit (in) 1 3/4 3 5/16 4 3/4 2 13/16 5/8 4 3/4 2 3/16 × 1/4 1 7/16 3 1/2 C:3D049544 2.6.4 Installation and Initial Setting 1. Remove the upper part of the remote controller. Insert a minus screwdriver (2 locations) into the recess between the upper part and the lower part of the remote controller and twist the screwdriver lightly. (The PC board is attached with the upper part of the remote controller.
Control Devices EDUS391000-C Attach the lower part to the electrical box (part to be procured in the field) with the provided installation screws. (Select a flat face as an installation place. Do not tighten the installation screws excessively not to damage the lower part of the remote controller.) For part to be procured in the field electrical box, use KJB211AA (optional accessory). 2. Initial Setting 1.
EDUS391000-C Control Devices 4. Forced reset switch (SS1) When changing the setting of the connector for individual use, etc., the switch can be reset simply by setting it to the reset side once and returning to the normal side. This procedure enables to reset without turning off the power. (Set the normal side at normal operation.) 5. Setting for special function When you want to have a programmed operation of a part of indoor units by using only schedule timer, cut off JP1 and supply the power again.
Control Devices EDUS391000-C Wiring Specifications F1, F2 D1, D2 Wiring Sheathed wire (2-wire) Sheathed wire (2-wire) Gauge AWG #18-#16 AWG #18-#16 Length Max. 3280 ft Max. 492 ft NOTES: 1. Electrical box and transmission wiring are not attached. 2. Do not touch the PC board with your hand. 3. Keep transmission wiring at least 2 inch away from power supply wiring to avoid malfunctions. 4. Install the Upper Part of the Remote Controller as before. 2.6.
EDUS391000-C 2.7 Control Devices DCS601C71 intelligent Touch Controller 2.7.1 Features This controller is a central remote controller offering higher functionality and easier operation than the previous DCS302C71controller. Up to 64 groups of indoor units may be connected to 1 unit of this controller.
Control Devices EDUS391000-C 2.7.2 System Overview This intelligent Touch Controller is capable of controlling/monitoring up to 64 groups of indoor units (hereafter “groups”). The main functions of the intelligent Touch Controller include: 1. Collective starting/stopping of operation of the indoor units connected to the intelligent Touch Controller. 2.
EDUS391000-C Control Devices 2.7.3 Options Connecting Unification adaptor allows using the contact for normal and abnormal operation signal and collective start/stop with a contact. For details, contact the vendor you purchased the product from. Monitoring from PC is possible by Web E-mail functions.
Control Devices EDUS391000-C 2.7.5 Part Names and Functions Front and Side View PCMCIA Card Slot Used when updating the intelligent Touch Controller software to a newer version. Color LCD with Touch Panel Touch Pen Provides a display for monitoring and operation. Be sure to use the touch pen provided for operation. Use the touch pen for operation. Be sure to use the touch pen for operation. Use caution not to lose the touch pen.
EDUS391000-C Control Devices 2.7.6 Part Names on the Monitoring Screen and the Functions Icon Contents of the List Currently Displayed Zone/Group Currently Displayed When Group List is displayed “Zone: Zone Name” When Zone List is displayed “Zone List Display” The name of the zone/group currently selected is highlighted in blue flame. Display Mode Selection Select between Zone and Group. System Condition Displayed Domain Domain displaying system condition (Compulsory Stop etc.
Control Devices EDUS391000-C Contents of the List Currently Displayed Zone/Group Currently Displayed Display Mode Selection When Group List is displayed “Zone: Zone Name” When Zone List is displayed “Zone List Display” The name of the zone/group currently selected is highlighted in blue frame. Press the button and display change between Zone and Group. Filter/Element Sign System Condition Displayed Domain Domain displaying system condition (Compulsory Stop etc.).
EDUS391000-C Control Devices List Contents of the List Currently Displayed Zone/Group Currently Displayed Display Mode Selection When Group List is displayed “Zone: Zone Name” When Zone List is displayed “Zone List” The name of the zone/group currently selected is highlighted in light-blue. Press the button and display change between Zone and Group. System Condition Displayed Domain Domain displaying system condition (Compulsory Stop etc.
Control Devices EDUS391000-C 2.7.
EDUS391000-C Controls Control Devices 63
Control Devices 64 EDUS391000-C Controls
EDUS391000-C Control Devices 1P167242A Controls 65
Control Devices EDUS391000-C 2.7.8 DCS004A71 Web Software Functions and Outline Using this software enables you to operate and monitor air conditioners linked to the intelligent Touch Controller on the Windows PC, which is connected with the intelligent Touch Controller and the Ethernet communication (LAN).
EDUS391000-C Adapter 3. Adapter 3.1 KRCS01-1B / 4B Remote Sensor FXMQ-PVJU AHU type, FXTQ-PAVJU 39ft. 4-1/2in.
Adapter EDUS391000-C 1-5/8 1-1/4 1/8-M4 Break open the knockout hole in the sensor with wire cutters. Pass the extension wires through the hold and fasten the wires to the terminals with screws. 1-5/8 (4-3/4) 1/8-M4 7/8 1-1/4 (2-3/4) metal plate on site (unit:in.
EDUS391000-C Adapter C:3K019189B Controls 69
Adapter 3.
EDUS391000-C Adapter To adaptor power supply connector on indoor unit or Branch Selector unit.
Adapter EDUS391000-C If installing on a Branch Selector unit, install the adaptor insie the control box of the Branch Selector unit.
EDUS391000-C 3.
Adapter EDUS391000-C 1P013360 74 Controls
EDUS391000-C Adapter 1P013360 Controls 75
Adapter 3.
EDUS391000-C Adapter C:2P263038A Controls 77
Adapter EDUS391000-C (KRP1C74) Compact multi flow C:2P263038A 78 Controls
EDUS391000-C 3.
Adapter EDUS391000-C Ceiling mounted duct type Ceiling mounted cassette type (Compact multi flow) Ceiling mounted AHU type FXDQ FXZQ FXTQ (KRP4A71) C FXMQ-M (KRP4A71) C:1P161220 80 Controls
EDUS391000-C Controls Adapter 81
Adapter 82 EDUS391000-C Controls
EDUS391000-C Adapter C:1P161221 Controls 83
Adapter 3.6 EDUS391000-C DCS302A72 Unification Adaptor for Computerized Control 3.6.1 Function When connected to the central remote controller, this kit enables unified display (operation/malfunction) and unified control (operation/stop). 1. Unified Display 2. Unified Control 3.6.
EDUS391000-C Adapter 3.6.3 Installation Securely install the adaptor inside the electric panel box (field supplied) with the 4 attached screws. Install the adaptor in a place within 16ft. from the central remote controller to enable cable connection. Note 1. Do not damage the PC board with your screwdriver, etc. 2. Install the adaptor inside an electric panel box to protect from electromagnetic waves and dust. 3.6.
Adapter EDUS391000-C (Wire specifications) AWG #18 or #16 gauge sheathed vinyl cord or cable (2-wire) Max. length: 490ft. 1. Control Input (Unified Operation/Stop) Wire as explained here following, depending on whether input carries a voltage (VOLT.) or not (NON VOLT.). (1) Input with Voltage Set the CHANGEOVER SWITCH (SS1) to VOLT. (Factory set: VOLT) (2) Input with Non Voltage Set the CHANGEOVER SWITCH to NON VOLT.
EDUS391000-C Adapter 2. Control Mode Switch (RS1) Setting (1) For Normal Operation by Input A Position Input A OFF ON: Unified Operation 2 ON OFF: Unified Stop Input B can be disregarded. (2) For Instantaneous Operation by Input A and B (Use an instantaneous input of 400 mili-sec. or more at ON time.) Position Input A Input B 3 On: Unified Operation ON: Unified Stop (3) Do not set the switch to position 1. This switch can be set at any time. 3.
Adapter 88 EDUS391000-C Controls
Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms tot he applicable standards, and is suitable for use, in the region where the product will be used.