Specifications

SiBE04-624 Check
Service Diagnosis 205
3.6 Main Circuit Electrolytic Capacitor Check
Check No.11
Do not touch the live parts within 10 min. after the breaker is turned off.
Even after that, when you touch the parts, check that there is no DC voltage with a tester.
Check the conductivity with a tester. It is OK if the tester shows good conductivity when pins
are replaced.
3.7 Refrigerant System Check
Check No.12
Set the tester to the
resistance measuring
range
If the pointer swings
and returns, the
electrolytic capacitor
is OK.
If the pointer does not
swing, or does not return,
the electrolytic capacitor is
out of order.
(R3466)
Rectify.
4-way valve operation fault,
replace it.
Conduct vacuum drying.
Replace the gas.
(R6022)
Refrigerant system check (blockage,
gas leakage, insufficient gas are to
be checked)
Is the temperature
of suction pipe of 4-way valve
extremely high?
Gas leakage check
Refer to the insufficient gas
detection
NO
YES
NO
Is the discharge pipe
thermistor disconnected
from the holder?
YES
Is any moisture
found in by SPORLAN?
No moisture
Moisture
Check after operating enough time.
Models with discharge pipe thermistor