Specifications

SiBE04-624 Control Specification
Function and Control 67
3.7 Input Current Control
Detail
Stop zone
z
After 5 seconds in this zone the compressor is stopped
Step down zone
z
The maximum limit of the compressor frequency in this control is defined as operation
frequency - 2 Hz.
z
After this, the output frequency is pulled down by 2 Hz every second until it reaches the
steady zone.
Steady zone
z
Keeping the present maximum frequency.
Return zone
z
Limit of the frequency is cancelled.
Class
Cooling Heating
28 42 50 28 42 50
I1 (A) 141414141414
I2 (A) 5.5 7.5 10.0 10.5 10.5 10.5
I3 4.5 6.5 9.0 9.5 9.5 9.5
Compressor Stop
Step down Zone
Stop Zone
Steady Zone
Return Zone
I1
I2
I3
(R5907)
Ambient temperature
I2
*I2 has the cooling and heating current,
respectively.
(R5917)