INSTALLATION MANUAL Unit for air to water heat pump system EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1
1 B2 D2 E C L1 H B1 L2 A 1 D1 B2 D2 E C L1 1 H B1 A L2 D1 2 1 2 V3 W1 AC AC AC 2 DC AC DC
CE - DECLARACION-DE-CONFORMIDAD CE - DICHIARAZIONE-DI-CONFORMITA CE - ¢H§ø™H ™YMMOPºø™H™ CE - ERKLÆRING OM-SAMSVAR CE - ILMOITUS-YHDENMUKAISUUDESTA CE - PROHLÁŠENÍ-O-SHODĚ CE - IZJAVA O SKLADNOSTI CE - VASTAVUSDEKLARATSIOON CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ CE - ATITIKTIES-DEKLARACIJA CE - ATBILSTĪBAS-DEKLARĀCIJA CE - VYHLÁSENIE-ZHODY CE - UYUMLULUK-BİLDİRİSİ 05 Nota * 04 Bemerk * 03 Remarque * 02 Hinweis * 01 Note * 19 ob upoštevanju določb: 20 vastavalt nõuetele: 21 следвайки клаузите на: 22 laikan
EDHQ011~016AA6V3 EDLQ011~016AA6V3 EBHQ011~016AA6V3 EBLQ011~016AA6V3 CONTENTS EDHQ011~016AA6W1 EDLQ011~016AA6W1 EBHQ011~016AA6W1 EBLQ011~016AA6W1 Installation manual Unit for air to water heat pump system Page READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE. Introduction ....................................................................................... 1 General information ..............................................................
SAFETY Options ■ CONSIDERATIONS Domestic hot water tank EKHW* An optional EKHW* domestic hot water tank with integrated 3 kW electrical booster heater can be connected to the unit. The domestic hot water tank is available in three sizes: 150, 200 and 300 litre.
Caution ■ Earthing resistance should be according to national regulations Do not connect the earth wire to gas or water pipes, lightning conductor or telephone earth wire. Incomplete earthing may cause electric shocks. ■ Gas pipe. Ignition or explosion may occur if the gas leaks. ■ Water pipe. Hard vinyl tubes are not effective earths. ■ Lightning conductor or telephone earth wire. Electric potential may rise abnormally if struck by a lightning bolt. ■ Be sure to install an earth leakage circuit breaker.
SELECTING 2 5 If you install the unit on a frame, please install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction. ■ Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals. 6 ■ Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
(B) In case of stacked installation Drain work 1. In case obstacles exist in front of the outlet side. Check in the combination table under "Possible options" on page 3 whether drain work is allowed. In case drain work on your unit is allowed and the installation site requires drain work, then follow the guidelines below. Drain kits for drainage are available as option.
TYPICAL APPLICATION EXAMPLES Application 2 When the AD system is used in series with another heat source (e.g. gas boiler), it shall be made sure that the return water temperature to the heat exchanger does not exceed 55°C. Daikin shall not be held liable for any damage resulting from not observing this rule. Space heating only application without room thermostat connected to the unit. The temperature in each room is controlled by a valve on each water circuit.
Domestic water heating Pump operation and space heating and cooling When domestic water heating mode is enabled (either manually by the user, or automatically through a schedule timer) the target domestic hot water temperature will be achieved by a combination of the heat exchanger coil and the electrical booster heater. According to the season, the customer will select cooling or heating on the room thermostat (T). This selection is not possible by operating the user interface.
Pump operation With no thermostat connected to the unit (1), the pump (3) can be configured to operate either as long as the unit is on, or until the required water temperature is reached. Details on pump configuration can be found under "Pump operation configuration" on page 19. NOTE Main components Hydraulic compartment (door 3) 1 19 Space heating and cooling 16 According to the season, the customer will select cooling or heating through the user interface.
13. Manometer The manometer allows readout of the water pressure in the water circuit. Switch box main components (door 2) A 14. Flow switch The flow switch checks the flow in the water circuit and protects the heat exchanger against freezing and the pump against damage. B D A 8 16. Backup heater vessel The backup heater heats the water in the backup heater vessel. 9 C S1T X4M 15. Pump The pump circulates the water in the water circuit. C E5H 9 8 18.
. X9A socket The X9A socket receives the thermistor connector (only for installations with domestic hot water tank). 14. Pump fuse FU2 (in line fuse) 15. Pump relay K4M Checking the water circuit The units are equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a licensed technician and must comply with all relevant European and national regulations. 16. Transformer TR1 The unit is only to be used in a closed water system.
2 Using the table below, determine if the expansion vessel prepressure requires adjustment. 3 Using the table and instructions below, determine if the total water volume in the installation is below the maximum allowed water volume. Installation Water volume height difference(a) ≤280 l >280 l Actions required: ≤7 m No pre-pressure adjustment required.
Protecting the water circuit against freezing Charging water Frost can damage the unit. For this reason, in colder climates the water circuit can be protected by means of adding glycol to the water. However, this unit is by default already foreseen with a freeze-up protection function. Refer to paragraph "[4-04] Freeze-up protection function" on page 23.
Precautions on electrical wiring work High voltage Maximum running current Description 1 Power supply cable for unit AC 2+GND (V3) 4+GND (W1) (a) 2 Power supply cable for backup heater AC 2+GND (V3) 3+GND (W1) (b) 3 Room thermostat cable AC 3 or 4 100 mA(c) 4 User interface cable DC 2 100 mA(c) Item To avoid electrical shock, make sure to disconnect the power supply 1 minute or more before servicing the electrical parts.
TC.................... Signal transmission circuit V1R.................. Power module V2R,V3R.......... Diode module V1T .................. IGBT X1M ................. Power supply terminal strip X1Y.................. Optional connector Y1E.................. Electronic expansion valve Y1S.................. Solenoid valve (4 way valve) Z1C~Z3C ......... Noise filter (ferrite core) Z1F~Z4F.......... Noise filter W1 models only A1P.................. Main PCB A2P.................. Inverter PCB A3P...............
Secure the wiring in the order shown below. ■ ■ ■ Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely (see figure 2). Specifications of standard wiring components Door 1: compressor compartment and electrical parts: X1M Follow the electric wiring diagram for electrical wiring works (the electric wiring diagrams are located on the rear side of doors 1 and 2).
Connection of the thermostat cable Door 2: electrical parts of the hydraulic compartment: X10M V3 W1 1~ 50 Hz 230 V 3N~ 50 Hz 400 V L1 L2 L3 1 Earth leakage circuit breaker 2 Fuse 1 2 Connection of the thermostat cable depends on the application. See also "Typical application examples" on page 6 and "Room thermostat installation configuration" on page 19 for more information and configuration options on pump operation in combination with a room thermostat.
Wiring the 3-way valve Possible types of benefit kWh rate power supply 1 Possible connections and requirements to connect the equipment to such power supply are illustrated in the figure below: Using the appropriate cable, connect the valve control cable to the appropriate terminals as shown on the wiring diagram. [D-01]=1 Two types of 3-way valves can be connected.
3 Benefit kWh rate power supplies that completely shut power supply like illustrated above as types 2 and 3 are not allowed for this application because of the water freeze prevention that would not be powered. ■ When connecting the equipment to a benefit kWh rate power supply, change field settings [D-01] and both [D-01] and [D-00] in case the benefit kWh rate power supply is of the type that power supply is not interrupted (like illustrated above as type 1).
START-UP AND CONFIGURATION The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user expertise. It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable. DIP switch settings overview The following table summarizes the required configuration and thermostat wiring at the terminal block in the switch box.
8 Domestic hot water tank installation configuration Refrigerant leak ■ When no domestic hot water tank is installed, toggle switch SS2-2 should be set to OFF (default). OFF ON ■ When a domestic hot water tank is installed, toggle switch SS2-2 should be set to ON. OFF ON Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer. 1 2 1 2 3 4 9 Power supply voltage Check the power supply voltage on the local supply panel.
Failure diagnosis at the moment of first installation Field settings ■ The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user demand. Thereto, a number of so called field settings are available. These field settings are accessible and programmable through the user interface.
Detailed description [2] Disinfection function [0] User permission level Applies only to installations with a domestic hot water tank. If required, certain user interface buttons can be made unavailable for the user. The disinfection function disinfects the domestic hot water tank by periodically heating the domestic water to a specific temperature. Three permission levels are defined (see the table below).
[4] Backup heater operation and space heating off temperature Backup heater operation The operation of the backup heater can altogether be enabled or disabled, or it can be disabled depending on operation of the booster heater. ■ [4-00] Status: defines whether backup heater operation is enabled (1) or disabled (0). NOTE Even in case the backup heater operation status field setting [4-00] is set to disabled (0), the backup heater can operate during start-up and defrost operation.
[6] DT for domestic water heating [7] Domestic hot water step length Applies only to installations with a domestic hot water tank. Applies only to installations with a domestic hot water tank. The 'DT (delta temperature) for domestic water heating' field settings determine the temperatures at which heating of the domestic water by the heat pump will be started (i.e., the heat pump ON temperature) and stopped (i.e., the heat pump OFF temperature).
[8] Domestic water heating mode timer Applies only to installations with a domestic hot water tank. ■ [8-03] Booster heater delay time: specifies the start-up time delay of the booster heater operation after start of the heat pump domestic water heating operation. The 'domestic water heating mode timer' field settings defines the minimum and maximum domestic water heating times, and minimum time between two domestic water heating cycli.
[9] Cooling and heating set points [D] Benefit kWh rate power supply The purpose of this field setting is to prevent the user from selecting a wrong (i.e., too hot or too cold) leaving water temperature. Thereto the heating temperature set point range and the cooling temperature set point range available to the user can be configured.
Field settings table Installer setting at variance with default value First code Second code Setting name 0 User permission level 1 Weather dependent set point 00 2 3 5 6 User permission level Default value Range Step Unit 3 2/3 1 — –20~5 1 °C 01 High ambient temperature (Hi_A) 15 10~20 1 °C 02 Set point at low ambient temperature (Lo_TI) 40 25~55 1 °C 03 Set point at high ambient temperature (Hi_TI) 25 25~55 1 °C Fri Mon~Sun, All — — Disinfection function 00 O
Installer setting at variance with default value First code C D E Second code Setting name Date Value Date Value Default value Range Step Unit Solar priority mode 00 Solar priority mode setting 0 0/1 1 — 01 Output logic of the EKRP1H remote alarm input/output PCB 0 0/1 — — Benefit kWh rate power supply 00 Switching off heaters 0 0/1/2/3 — — 01 Unit connection to benefit kWh rate power supply 0 (OFF) 0/1/2 — — 02 Not applicable.
TEST RUN AND FINAL CHECK The installer is obliged to verify correct operation of unit after installation. Final check Before switching on the unit, read following recommendations: ■ When the complete installation and all necessary settings have been carried out, close all front panels of the unit and refit the unit cover. ■ The service panel of the switch box may only be opened by a licensed electrician for maintenance purposes.
8 Unit switch box ■ Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring. ■ Check for correct operation of contactors K1M, K3M, K5M (applications with domestic hot water tank only) and K4M by use of an ohmmeter. All contacts of these contactors must be in open position.
Symptom 4: The water pressure relief valve opens POSSIBLE CAUSES Error codes CORRECTIVE ACTION The expansion vessel is broken. Replace the expansion vessel. The water volume in the installation is too high. Make sure that the water volume in the installation is under the maximum allowed value (refer to "Checking the water volume and expansion vessel pre-pressure" on page 10). When a safety device is activated, the user interface LED will be flashing, and an error code will be displayed.
Error code Failure cause Corrective action Error code Failure cause Corrective action Booster heater thermal protector is open (applies only to installations with a domestic hot water tank) Reset the thermal protector P1 PCB failure Contact your local dealer. P4 Electric component failure Contact your local dealer. PJ Failure of capacity setting Contact your local dealer.
TECHNICAL SPECIFICATIONS General ED_011 V3 models (1~) ED_016 EB_011 ED_014 EB_014 EB_016 ED_011 W1 models (3N~) ED_016 EB_011 ED_014 EB_014 EB_016 Nominal capacity • cooling • heating Dimensions H x W x D Weight Refer to the Technical Data Refer to the Technical Data 1418 x 1435 x 382 Refer to the Technical Data Refer to the Technical Data 1418 x 1435 x 382 180 kg 185 kg 180 kg 185 kg G 5/4" FBSP(a) hose nipple Ø9.5 mm (3/8 inch) Ø15.9 mm (5/8 inch) G 5/4" FBSP(a) hose nipple Ø9.
NOTES
4PW51121-1C Copyright © Daikin