EEDEN09-720 technical data AlthermaTM
AlthermaTM Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrige-rants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.
EEDEN09-720 technical data AlthermaTM
• AlthermaTM rA e0 h1 t4 l- RA Heating only Heat pump 4 • AlthermaTM
• AlthermaTM AlthermaTM Small Capacity Indoor - Outdoor Heating only Heating and Cooling PAGE 1 2 Oudoor unit - 1~ 1 ERHQ006-008AD 9 Indoor unit - 1~ 1 EKHBH(X)008AA 21 3 AlthermaTM Large Capacity Indoor - Outdoor Heating only Heating and Cooling Oudoor unit - 1~ 2 ERHQ011-016AA 35 Oudoor unit - 3~ 2 ERHQ011-016AAW1 53 Indoor unit - 1~ 2 EKHBH(X)016AB 69 5 Without bottom plate heater - 1~ 3 EDHQ011-016AA6V3 83 6 Without bottom plate heater - 3~ 3 EDHQ011-016AA6W1 103 Bott
EEDEN09-720 technical data AlthermaTM Part 1/4: ERHQ006-008AD EKHBH/X008AA
• Outdoor units • ERHQ006-008AD TABLE OF CONTENTS ERHQ006-008AD 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Outdoor units • ERHQ006-008AD 1 D iA n8 0u 0 a - r m 6 o r 0 o e 0 dh Q t H uRl EA•O 1 Features Small capacity outdoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 1 10 • AlthermaTM • Outdoor units
• Outdoor units • ERHQ006-008AD 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT For combination indoor units + outdoor units Indoor Units Condition 1 Heating capacity Nominal Capacity ERHQ007AD ERHQ008AD EKHBH008AA kW 4.36 4.36 Nominal kW 5.75 6.84 8.43 Maximum kW 7.45 8.79 9.58 Heating PI Nominal 1.26 1.58 2.08 COP Nominal 4.56 4.34 4.05 Heating capacity Minimum kW 3.87 3.87 3.87 Nominal kW 4.36 kW 5.03 6.10 7.64 Maximum kW 6.68 7.98 8.
• Outdoor units • ERHQ006-008AD 2 2-2 1 Specifications TECHNICAL SPECIFICATIONS Heat Exchanger Dimensions Length mm Nr of Rows 2 Fin Pitch mm Nr of Stages ERHQ006AD ERHQ007AD ERHQ008AD 845 845 845 2 2 2 1.8 1.8 1.
• Outdoor units • ERHQ006-008AD 2 2-2 Specifications TECHNICAL SPECIFICATIONS Standard Accessories ERHQ006AD Item ERHQ007AD ERHQ008AD Installation manual Quantity 1 Item 1 1 2 Drain plug Quantity 1 Notes 1 1 1 See operation range drawing The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
• Outdoor units • ERHQ006-008AD 3 Capacity tables 3-1 Cooling/Heating capacity tables COOLING 1 Model 3 006 007 008 Tamb (°C) LWE (°C) 7 11 13 16 20 7 11 13 16 20 7 11 13 16 20 20 CC 6.01 6.81 7.23 7.88 8.80 7.15 8.09 8.57 9.33 10.4 8.24 9.26 9.79 10.6 11.7 25 PI 1.56 1.57 1.57 1.56 1.55 2.05 2.09 2.11 2.13 2.16 2.43 2.49 2.52 2.57 2.63 CC 5.73 6.50 6.90 7.54 8.42 6.84 7.73 8.20 8.92 9.9 7.90 8.87 9.38 10.17 11.3 30 PI 1.75 1.77 1.78 1.78 1.79 2.28 2.34 2.36 2.40 2.44 2.68 2.76 2.80 2.86 2.
• Outdoor units • ERHQ006-008AD 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing unit (mm) ERHQ006-008 AD Drain outlet (I.D. J 15.9 hose for connection) 4 Wall height on air outlet side = less than 1200 Minimum space for air passage 1 In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10) Name plate Brand name label Wiring inlet Terminal strip with earth terminal Outdoor air temperature thermistor Liquid stop valve (J6.
• Outdoor units • ERHQ006-008AD 1 4 Dimensional drawing & centre of gravity 4-2 Centre of gravity ERHQ006-008 AD 4 The position of foundation bolt 4D042258L 16 • AlthermaTM • Outdoor units
• Outdoor units • ERHQ006-008AD 5 Piping diagram ERHQ006-008AD 1 Outdoor unit Heat exchanger 5 Outdoor air temperature thermistor Capillary tube 1 Capillary tube 2 Capillary tube 3 Heat exchanger thermistor Muffler with filter Refrigerant flow Cooling Heating Capillary tube 4 Filter Motor operated valve Propeller fan Filter Four way valve on : heating Muffler with filter Field piping Muffler Liquid stop valve Muffler Field piping Discharge pipe thermistor Compressor Accumulator Gas st
• Outdoor units • ERHQ006-008AD 1 6 Wiring diagram 6-1 Wiring diagram ERHQ006-008AD 6 Power supply To indoor unit Sheet metal Indoor g Field wiring (outdoor) (discharge) (Condenser) Outdoor Z1C∼Z7C X1M, X2M Y1E V2, V3, V5, V9, V100 SA2 FU1, FU2, FU3: AC1, AC2 U, V, W, X11A, X12A E1, E2 HR1, HR2 18 : Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Surge arrester : Fuse : Connector MRM10, MRM20 MRC/W R1T∼R3T S2∼S102 LEDA L N SW1 SW4 M1C M1F L1R : Magnetic relay :
• Outdoor units • ERHQ006-008AD 7 Sound data 7-1 Sound pressure spectrum ERHQ008AA HEATING 1 Sound pressure level (dB) Sound pressure level (dB) ERHQ007AA HEATING Sound pressure level (dB) ERHQ006AA HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) 7 Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 2
• Indoor units • EKHBH-X008AA TABLE OF CONTENTS EKHBH-X008AA 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . .
• Indoor units • EKHBH-X008AA 1 t A i A n8 0u a 0 m X r r - o e H o h B d tH nKl E•IA 1 Features Small capacity indoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 1 22 • AlthermaTM • Indoor units
• Indoor units • EKHBH-X008AA 2 2-1 Specifications TECHNICAL SPECIFICATIONS EKHBH008AA Outdoor units ERHQ008ADV3 Nominal input (Indoor only) Casing W 230 Colour Packing Unit Weight Packing 230 RAL9010 Material Dimensions EKHBX0008AA 1 2 Epoxy polyester painted galvanised steel Height mm Width mm 660 1,225 660 Depth mm 610 610 Height mm 922 922 Width mm 502 502 Depth 361 mm 361 Unit kg 52 52 Packed Unit kg 67 67 Material EPS Wood Carton PP (Straps) Weight kg
• Indoor units • EKHBH-X008AA 2 2-1 1 Specifications TECHNICAL SPECIFICATIONS Operation range 2 Ambient Waterside 2-2 °C Cooling °C Heating °C Cooling °C ELECTRICAL SPECIFICATIONS Electric heater Current Current Electric heater EKHBH008AA EKHBX0008AA 3V3 Phase 1~ Frequenc Hz y 50 50 Voltage V 230 230 Running Current A 13 13 List No requirements 0.25 + j0.
• Indoor units • EKHBH-X008AA 2 2-2 Specifications ELECTRICAL SPECIFICATIONS Wiring connections For power supply backup heater Electric heater Type Power Supply EKHBH008AA Quantity of wires Type of wires Current Electric heater Wiring connections Electric heater Phase Electric heater Wiring connections Electric heater Voltage V 230 230 Running Current A 15.1 15.
• Indoor units • EKHBH-X008AA 2 2-2 1 Specifications ELECTRICAL SPECIFICATIONS Wiring connections 2 For power supply backup heater EKHBH008AA Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type For power supply connection to Optional Warm Water Tank + Q2L Quantity of wires 3G Type of wires Select diameter and type according to national and local regulations Type of wires (4) For more details of the voltage range and current re
• Indoor units • EKHBH-X008AA 3 Options Factory mounted optional equipment for EKHB(H/X)008AA** Reference 1 Description Heating only model EKHBH008A... Reversible model EKHBX008A...
• Indoor units • EKHBH-X008AA 1 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHBH008AA FIXATION 4 Service door (Closed) 361 (Open) 553 G 1 (Male) Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection G 1 1/2 (female) j 4 Water OUT connection G 1 1/2 (female) j 5 Power supply intake (+ domestic hot water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gaug
• Indoor units • EKHBH-X008AA 5 Piping diagram EKHBH(X)008AA R4T R3T R2T R1T Water side 1 Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat-exchanger thermistor Field installation 5 Filter Inlet Shut off valve Refrigerant side Safety valve Drain valve Pressure gauge Drain Expansion vessel Cooling (EKHBX) Heating (EKHBX + EKHBH) Option backup heater Drain valve Field installation Air purge Flowswitch Pump Outlet Shut off valv
• Indoor units • EKHBH-X008AA 1 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)008AA3V3 Power supply 230V 1N∼50Hz Only for EKSOLHWAV1 Option Outdoor unit Solar pump connection >> See note 2 << Domestic hot water tank Only See note 9 6 for EKHW Option Only for EKHW(S/E) Option See note 7 For EKHWSU*V3 Option User interface Alarm output Solar input Cooling/heating on/off output Only for EKHW Option Only for EKRTW Option 230V AC heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note
• Indoor units • EKHBH-X008AA 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)008AA6WN/9WN Power supply 3(/N)∼400(/230V) 50Hz Domestic hot water tank Only for EKSOLHWAV1 Option Outdoor unit 1 Domestic hot water tank Solar pump connection >> See note 2 << Only See note 9 for EKHWE Option 6 Only for EKHWS*Z2 Option Only for EKHW(S/E)* Option See note 7 Only for EKHW Option Only for EKRTW Option 230V AC heating cooling Only for EKRP1HB & ESOLHWAV1 Option See note 8 supply from PCB Only for
• Indoor units • EKHBH-X008AA 1 6 6 Wiring diagram 6-2 External connection diagram EKHBH(X)008AA Standard parts Power supply Outdoor unit 3 core Unit power supply: 230V + earth For more details please check unit wiring diagram X1M:L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Optional power supply X2M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth 4 core 3 or4 core 3 core Optional parts Field supply X1M:9-10-11-Earth Sanitary tank 2 way valve 2 c
• Indoor units • EKHBH-X008AA 7 Operation range Outdoor temp. (°CDB) EKHBH(X)008AA ERHQ006-008AD 1 Cooling mode 7 Leaving evaporator water temperature (°C) Outdoor temp. (°CDB) Heating mode : Units with optional back up heater Leaving condenser water temperature (°C) 50 Domestic hot water Outdoor temp.
• Indoor units • EKHBH-X008AA 1 8 Hydraulic performance 8-1 Static pressure drop unit EKHBH(X)008AA ESP [kPa] 8 Flow (l/min) III: High speed II: medium speed I: Low speed ESP: External static pressure Flow: waterflow through the unit Warning: 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
EEDEN09-720 technical data AlthermaTM Part 2/4: ERHQ011-016AA ERHQ011-016AAW1 EKHBH(X)016AB
• Outdoor units • ERHQ011-016AAV3 TABLE OF CONTENTS ERHQ011-016AAV3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Outdoor units • ERHQ011-016AAV3 1 A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H uRl EA•O Features Single phase large capacity outdoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 2 1 38 • AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAV3 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT ERHQ011AA ERHQ014AA ERHQ016AA For combination indoor units + outdoor units Indoor Units Condition 1 Heating capacity Nominal kW 11.2 14.0 16.0 Heating PI Nominal kW 2.46 3.17 3.83 COP Nominal 4.55 4.42 4.18 Heating capacity Nominal kW 10.3 13.1 15.2 Heating PI Nominal kW 3.06 3.88 4.66 COP Nominal 3.37 3.38 3.
• Outdoor units • ERHQ011-016AAV3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Heat Exchanger Dimensions Length mm Nr of Rows Fin Pitch 2 mm Nr of Passes Face Area 2 m² Nr of Stages ERHQ011AA ERHQ014AA ERHQ016AA 857 857 857 2 2 2 1.4 1.4 1.4 6 6 6 0.98 0.98 0.
• Outdoor units • ERHQ011-016AAV3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Piping connections Liquid (OD) Quantity ERHQ011AA ERHQ014AA ERHQ016AA 1 1 1 Type Flare connection Diameter (OD) Gas mm Quantity 9,52 1 Type mm Quantity 2 3 3 3 Hole Diameter (OD) mm Minimum 26 26 26 m 5 5 5 Maximum m 75 75 75 Equivalent m 95 95 95 Chargeless m 30 30 30 Additional Refrigerant Charge Installation height difference 2 15,9 Type Piping Length 1 Flare connection Di
• Outdoor units • ERHQ011-016AAV3 3 Capacity tables 3-1 Heating capacity tables Maximum Heating Capacity (Peak values) Model 2 3 ERHQ11 ERHQ14 ERHQ16 LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 30 HC 5.66 6.48 8.04 9.18 10.2 11.6 13.1 14.1 15.9 7.24 8.19 10.1 11.5 12.7 14.4 16.3 17.6 19.9 8.35 9.38 11.5 13.0 14.4 16.3 18.5 20.0 22.5 35 PI 2.17 2.21 2.24 2.24 2.23 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.87 2.87 2.88 2.86 2.85 2.82 3.25 3.33 3.42 3.46 3.
• Outdoor units • ERHQ011-016AAV3 3 Capacity tables 3-2 Cooling capacity tables Maximum Cooling Capacity ERHQ11 ERHQ14 ERHQ16 Tamb (°C) LWE (°C) 7 10 13 15 18 22 7 10 13 15 18 22 7 10 13 15 18 22 20 CC 11.7 12.9 14.1 14.9 16.2 18.0 14.5 16.0 17.6 18.6 20.2 22.5 15.3 16.9 18.5 19.6 21.0 23.3 25 PI 2.56 2.58 2.59 2.60 2.61 2.62 3.85 3.94 4.02 4.08 4.17 4.29 4.37 4.48 4.60 4.68 4.97 5.21 CC 11.2 12.3 13.4 14.2 15.5 17.2 13.9 15.3 16.8 17.8 19.3 21.5 14.7 16.2 17.7 18.7 20.0 22.2 30 PI 2.86 2.89 2.
• Outdoor units • ERHQ011-016AAV3 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing ERHQ011-016 Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8 2 4 Gas pipe connection ∅15.9 flare Liquid pipe connection ∅9.
• Outdoor units • ERHQ011-016AAV3 4 Dimensional drawing & centre of gravity 4-2 Centre of gravity ERHQ011-016 2 4 4TW57919-5 • AlthermaTM • Outdoor units 45
• Outdoor units • ERHQ011-016AAV3 5 Piping diagram ERHQ011-016AAV3 2 Electronic expansion valve 5 Filter Filter Heat exchanger 4-Way-Valve High Pressure Low Pressure Switch Sensor EKHB 016 Field Piping ø9.5 C 1220T-0 Service Port 5/16’ Compressor Field Piping ø15.9 C 1220T-0 Accumulator Outdoor Unit Indoor Unit Heating Cooling Stop Valve (With Service Port 5/16’ Flare) Check Valve Flare Conn. Screw Conn. Flange Conn.
• Outdoor units • ERHQ011-016AAV3 6 Wiring diagram 6-1 Wiring diagram ERHQ011-016AAV3 Option EKBPHT16Y Only for *RHQ01*AAV3(7) Only for *RHQ01*AAV38 Indoor Outdoor (Note 4) HAP Position of compressor El. comp.
• Outdoor units • ERHQ011-016AAV3 7 Sound data 7-1 Sound pressure spectrum ERHQ011-016 ERHQ011AAV3 HEATING ERHQ014AAV3 HEATING ERHQ016AAV3 HEATING 2 Octave band center frequency (Hz) Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) 7 Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-2A NOTES 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level.
• Outdoor units • ERHQ011-016AAV3 7 Sound data 7-2 Sound pressure night quiet mode ERHQ011-016 ERHQ011AAV3 HEATING ERHQ014AAV3 HEATING ERHQ016AAV3 HEATING 2 Octave band center frequency (Hz) Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) 7 Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-4 NOTES 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level.
• Outdoor units • ERHQ011-016AAV3 8 Installation 8-1 Service space ERHQ011-016 A. Non stacked installation Legend 2 Unit: mm Suction side obstacle 8 Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Outdoor units • ERHQ011-016AAV3 9 Operation range ERHQ011-016AAV3 Outdoor temp. (°CDB) 2 Cooling mode 9 Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) Heating mode No heat pump operation, back up heater only * ERHQ_V18 units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Outdoor units • ERHQ011-016AAW1 TABLE OF CONTENTS ERHQ011-016AAW1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Outdoor units • ERHQ011-016AAW1 1 A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H uRl EA•O Features Three phase large capacity outdoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 2 1 54 • AlthermaTM • Outdoor units
• Outdoor units • ERHQ011-016AAW1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT For combination indoor units + outdoor units Condition 1 Nominal Capacity For combination indoor units + outdoor units Condition 1 Nominal Capacity ERHQ011AAW1 Indoor Units ERHQ014AAW1 ERHQ016AAW1 EKHBH016AB Heating capacity Nominal kW 11.32 14.50 16.05 Heating PI Nominal kW 2.54 3.33 3.73 2 COP Nominal 4.46 4.35 4.30 2 Heating capacity Nominal kW 10.98 13.57 15.
• Outdoor units • ERHQ011-016AAW1 2 2-2 Specifications TECHNICAL SPECIFICATIONS Motor Speed (nominal) ERHQ011AAW1 ERHQ014AAW1 8 8 8 rpm 760 760 760 Cooling rpm 780 780 780 Output W 70 70 70 Steps Heating 2 2 Fan Motor Drive Compressor Direct drive Quantity Motor 1 1 Model JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 1 2,200 Starting Method Inverter driven Motor Crankcase Heater Output W 33 33 33 Operation Range Heating Min °CWB -2
• Outdoor units • ERHQ011-016AAW1 2 2-2 Specifications TECHNICAL SPECIFICATIONS ERHQ011AAW1 Safety Devices ERHQ014AAW1 ERHQ016AAW1 High pressure switch Fan motor thermal protector Fuse Standard Accessories Item Tie-wraps Quantity 2 2 Item 2 Installation manual Quantity 1 Notes 1 2 2 1 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment.
• Outdoor units • ERHQ011-016AAW1 3 Capacity tables 3-1 Heating capacity tables ERHQ011-016AAW1 Maximum Heating Capacity (Peak values) Model 2 LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW57912-1A SYMBOLS CC HC PI LWE LWC Tamb 58 NOTES : Cooling capacity at maximum ope
• Outdoor units • ERHQ011-016AAW1 3 Capacity tables 3-2 Cooling capacity tables ERHQ011-016AAW1 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 2 3 3TW57912-1A NOTES SYMBOLS CC HC PI LWE LWC Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc.
• Outdoor units • ERHQ011-016AAW1 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing ERHQ011-016AAW1 1. 2. 3. 4. 5. 6. 7. 8. Hole for anchor bolt 4-M12 2 Gas pipe connection J15.9 flare Liquid connection pipe "9.
• Outdoor units • ERHQ011-016AAW1 4 Dimensional drawing & centre of gravity 4-2 Centre of gravity ERHQ011-016 2 4 4TW57919-5 • AlthermaTM • Outdoor units 61
• Outdoor units • ERHQ011-016AAW1 5 Piping diagram ERHQ011-016AAW1 2 5 R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC Y1S Y3S S1PH M*F M*C : Thermistor (Air) : Thermistor (discharge) : Thermistor (Suction) : Thermistor (Liquid 1) : Thermistor (middle) : Thermistor (Liquid 2) : Pressure sensor : : Crankcase heater : 4-way valve : Injection valve : High pressure switch : Fan motor :Compressor filter (strainer) filter (strainer) Heat exchanger Distributor Capillary tube Service port 5/16″ Field piping J 9
• Outdoor units • ERHQ011-016AAW1 6 Wiring diagram 6-1 Wiring diagram ERHQ011-016AAW1 EKBPHT16Y Only for *RHQ01*AAW1 Power supply 3N∼ 400V 50Hz Only for *RHQ01*AAW18 Indoor Outdoor Reactor terminal position Note: 4 Notes: 1 This wiring diagram only applies to the outdoor unit 2 L: Live, N: Neutral, g: Field wiring 3 D : Terminal strip F : Connector GM: Connection R : Protective earth (screw) : Connector p : Noiseless earth G : Terminal 4 Refer to the option manual, for connecting wiring to x6A and
• Outdoor units • ERHQ011-016AAW1 7 Sound data 7-1 Sound pressure spectrum ERHQ016AAW1* HEATING Sound pressure level (dB) 7 ERHQ014AAW1* HEATING Sound pressure level (dB) 2 Sound pressure level (dB) ERHQ011AAW1* HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressur
• Outdoor units • ERHQ011-016AAW1 7 Sound data 7-2 Sound pressure night quiet mode ERHQ016AAW1* HEATING Sound pressure level (dB) Sound pressure level (dB) ERHQ014AAW1* HEATING Sound pressure level (dB) ERHQ011AAW1* HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) 2 7 Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic
• Outdoor units • ERHQ011-016AAW1 8 Installation 8-1 Service space ERHQ011-016 A. Non stacked installation Legend 2 Unit: mm Suction side obstacle 8 Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Outdoor units • ERHQ011-016AAW1 9 Operation range ERHQ011-016AAW1 Outdoor temp. (°CDB) 2 Cooling mode 9 Leaving evaporator Water temperature (°C) 6 Outdoor temp. (°CDB) Units with optional back up heater Heating mode operation possible, but no guarantee of capacity (if outdoor temperature < -25°C unit will stop) ERHQ_W18 units include special equipment (insulation heater sheet, à) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Indoor units • EKHBH-X016AB TABLE OF CONTENTS EKHBH-X016AB 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . .
• Indoor units • EKHBH-X016AB 1 t B i A n6 1u a 0 m X r r - o e H o h B d tH nKl E•IA Features Large capacity indoor unit • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 2 1 70 • AlthermaTM • Indoor units
• Indoor units • EKHBH-X016AB 2 2-1 Specifications TECHNICAL SPECIFICATIONS EKHBH016AB Outdoor units ERHQ16AAV3 Nominal input (Indoor only) Casing Colour Dimensions Packing W 230 2 Epoxy polyester painted galvanised steel Unit Packing 230 RAL9010 Material Weight EKHBX016AB Height mm 1,225 Width mm 660 Depth mm 610 610 Height mm 922 922 660 Width mm 502 502 Depth mm 361 361 Unit kg 55 55 Packed Unit kg 65 65 Material 2 EPS Wood Carton PP (Straps) Weight
• Indoor units • EKHBH-X016AB 2 2-2 Specifications ELECTRICAL SPECIFICATIONS Electric heater Type EKHBX016AB 3V3 Power Supply Phase 1~ Frequency Hz 50 50 Voltage V 230 230 Current back-up heater Running Current A 13 13 Current back-up heater + booster heater (EKHWS* models) Z-max Text Running Current *V3 Minimum Ssc value *V3 Electric heater Voltage range Minimum -10% Maximum +10% 2 2 Wiring connections Electric heater For power supply backup heater 0.29 A 0.
• Indoor units • EKHBH-X016AB 2 2-2 Specifications ELECTRICAL SPECIFICATIONS Electric heater EKHBH016AB Type EKHBX016AB 9WN Power Supply Phase 3~ Frequency Hz 50 50 Voltage V 400 400 Current back-up heater Running Current A 13 13 Current back-up heater + booster heater (EKHWS* models) Running Current *V3 A *Z2 A Electric heater Voltage range Wiring connections Electric heater Minimum Ssc value For power supply backup heater 20.5 (13+7.
• Indoor units • EKHBH-X016AB 3 Options Factory mounted optional equipment for EKHB(H/X)016AB** Reference 2 3 Description Heating only model EKHBH016A... Reversible model EKHBX016A...
• Indoor units • EKHBH-X016AB 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHBH016AB FIXATION 2 4 Service door (Closed) 361 (Open) 553 1-1/4″ Male BSP View A Scale 1/5 Dimensions wallbracket Minimum space for service & ventilation Min. 150 Min.
• Indoor units • EKHBH-X016AB 5 Piping diagram EKHBH(X)016AB Water Site Expansion Vessel Pressure Gauge 2 5 Drain Safety Valve Flowswitch Evaporator Condensor Air Purge Blow Off Field Installation R2T Refriferant Side R1T Pump Refr. Out Water Outlet Refr. In Electric Heater Body Shut Off Valve With Drain/Fill Valve Plate Heat Exchanger R3T Field Installation R4T Filter Refr. In Water Inlet Refr.
• Indoor units • EKHBH-X016AB 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)016AB3V3 Only for EKSOLHWAV1 Option Outdoor unit Power supply 230V 1N∼50Hz Domestic hot water tank Solar pump connection >> See note 2 << Only for *EKHWE* Option See note 9 Only for *EKHW(S/E) Option See note 7 For EKHWSU*V3 Option 2 User interface 6 Only for EKRTW Option Solar input Alarm output Cooling/heating on/off output Only for EKHW Option heating cooling Only for EKRP1HB & EKSOLHWAV1 Option See note 8 2
• Indoor units • EKHBH-X016AB 6 Wiring diagram 6-1 Wiring diagram EKHBH(X)016AB6T1/9T1 Power supply Only for EKSOLHWAV1 Option Outdoor unit Domestic hot water Solar pump connection tank >> See note 2 << See note 9 Only for EKHW*V3 Option See note 7 For EKHWSU*V3 Option 2 User interface Only for EKHW Option Only forEKRTW Option Solar input Cooling/heating on/off output Alarm output 6 Only for EKRP1HB & EKSOLWAV1 Option 230V AC supply from PCB See note 8 Only for EKRTR Option Domestic
• Indoor units • EKHBH-X016AB 6 Wiring diagram 6-2 External connection diagram Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply unit power supply: 400V or 230V + earth 5 or 3 core 2 X1M:L1-L2-L3-N-Earth Optional power supply Backup heater power supply (3/6/9kW): 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) Bottom plate heater option Optional power supply
• Indoor units • EKHBH-X016AB 7 Installation 7-1 Drainage instructions EKHBDP 2 Leaving water temperature limit to prevent condesation 7 Relative humidity 40% Relative humidity 60% Relative humidity 80% Leaving water temperature [°C] Leaving water temperature [°C] Maximum leaving water temperature cooling mode = 22°C Example: With ambient temperature of 25°C and relative humidity of 40%. If leaving water temperature is below 12°C, condensation on water piping will happen.
• Indoor units • EKHBH-X016AB 8 Operation range EKHBH(X)016AB Outdoor temp. (°CDB) 2 Cooling mode 8 Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) Heating mode No heat pump operation, back up heater only * ERHQ_V18 units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Indoor units • EKHBH-X016AB 9 Hydraulic performance 9-1 Static pressure drop unit EKHBH(X)016 2 ESP [kPa] 9 Flow [l/min] l high speed ll medium speed ESP: external static pressure Flow: waterflow through the unit Warning: 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
EEDEN09-720 technical data AlthermaTM Part 3/4: EDHQ011-016AA6V3 EDHQ011-016AA6W1 EDLQ011-016AA6V3 EDLQ011-016AA6W1 EBHQ011-016AA6V3 EBHQ011-016AA6W1 EBLQ011-016AA6V3 EBLQ011-016AA6W1
• Monobloc • EDHQ011-016AA6V3 TABLE OF CONTENTS EDHQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EDHQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnH Dlo E•MA Features Heating only monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 86 • AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 16.00 Heating capacity Nominal kW 11.20 14.00 Heating PI Nominal kW 2.47 3.20 3.79 COP Nominal 4.54 4.37 4.22 15.06 Heating capacity Nominal kW 10.87 13.10 Heating PI Nominal kW 3.22 3.91 4.62 COP Nominal 3.37 3.35 3.
• Monobloc • EDHQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.
• Monobloc • EDHQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power EDHQ011AA6V3 Name Current Power supply Current back-up hydraulic component heater Current back-up heater Power Supply 1 1 1 50 50 230 230 Frequency Hz 50 Voltage V 230 Minimum V Maximum V -10% +10% Minimum Ssc kVa value Recomended A fuses Wiring connections EDHQ016AA6V3 V3 Phase Voltage range EDHQ014AA6V3 3 Equipment complying with EN/IEC 61000-3-12(*)
• Monobloc • EDHQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDHQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 2G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDHQ016AA6V3 -10% Quantity of wires 3 EDHQ014AA6V3 3G Type of wires
• Monobloc • EDHQ011-016AA6V3 3 Options EDHQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EDHQ011-016AA6V3 3 Options EDHQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EDHQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EDHQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EDHQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDHQ011-016AA6V3 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EDHQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EDHQ011-016AA6V3 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Ther
• Monobloc • EDHQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EDHQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.
• Monobloc • EDHQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EDHQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater
• Monobloc • EDHQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EDHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EDHQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EDHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EDHQ011-016AA6V3 9 Installation 9-1 Service space EDHQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EDHQ011-016AA6V3 10 Operation range EDHQ011-016AA6V3 3 Outdoor temp. (°CDB) Cooling mode only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDHQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EDHQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EDHQ011-016AA6W1 TABLE OF CONTENTS EDHQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EDHQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnH Dlo E•MA Features Heating only monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 104 • AlthermaTM • Monobloc
• Monobloc • EDHQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 16.00 Heating capacity Nominal kW 11.20 14.00 Heating PI Nominal kW 2.51 3.22 3.72 COP Nominal 4.46 4.35 4.30 15.06 Heating capacity Nominal kW 10.87 13.10 Heating PI Nominal kW 3.12 3.98 4.58 COP Nominal 3.48 3.29 3.
• Monobloc • EDHQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.
• Monobloc • EDHQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power Voltage range EDHQ011AA6W1 EDHQ014AA6W1 Name W1 Phase 3N~ EDHQ016AA6W1 Frequency Hz 50 50 50 Voltage V 400 400 400 Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A 5.8 5.8 5.
• Monobloc • EDHQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDHQ011AA6W1 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDHQ016AA6W1 -10% Quantity of wires 3 EDHQ014AA6W1 3G Type of wires
• Monobloc • EDHQ011-016AA6W1 3 Options EDHQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EDHQ011-016AA6W1 3 Options EDHQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EDHQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EDHQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EDHQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDHQ011-016AA6W1 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EDHQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EDLH011-016AA6W1 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor
• Monobloc • EDHQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EDHQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.
• Monobloc • EDHQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EDHQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater
• Monobloc • EDHQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EDHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EDHQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EDHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EDHQ011-016AA6W1 9 Installation 9-1 Service space EDHQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EDHQ011-016AA6W1 10 Operation range Outdoor temp. (°CDB) Cooling mode EDHQ011-016AA6W1 3 only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDHQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EDHQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EDLQ011-016AA6V3 TABLE OF CONTENTS EDLQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EDLQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnL Dlo E•MA Features Heating only monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 122 • AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 16.00 Heating capacity Nominal kW 11.20 14.00 Heating PI Nominal kW 2.47 3.20 3.79 COP Nominal 4.54 4.37 4.22 15.06 Heating capacity Nominal kW 10.87 13.10 Heating PI Nominal kW 3.22 3.91 4.62 COP Nominal 3.37 3.35 3.
• Monobloc • EDLQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.
• Monobloc • EDLQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power EDLQ011AA6V3 Name EDLQ014AA6V3 EDLQ016AA6V3 V3 Phase 1 1 1 50 50 230 230 Frequency Hz 50 230 Voltage V Voltage range Minimum V Maximum V Current Minimum Ssc value kVa Recomende d fuses A Wiring connections For power supply compressor component Power supply hydraulic component Current back-up heater Type Current back-up heater Power Supply -10% +10%
• Monobloc • EDLQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDLQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 2G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDLQ016AA6V3 -10% Quantity of wires 3 EDLQ014AA6V3 3G Type of wires
• Monobloc • EDLQ011-016AA6V3 3 Options EDLQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EDLQ011-016AA6V3 3 Options EDLQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EDLQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EDLQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EDLQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDLQ011-016AA6V3 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EDLQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EDLQ011-016AA6V3 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Ther
• Monobloc • EDLQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EDLQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.
• Monobloc • EDLQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EDLQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater
• Monobloc • EDLQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EDLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EDLQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EDLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EDLQ011-016AA6V3 9 Installation 9-1 Service space EDLQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EDLQ011-016AA6V3 10 Operation range EDLQ011-016AA6V3 3 Outdoor temp. (°CDB) Cooling mode only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDLQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EDLQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EDLQ011-016AA6W1 TABLE OF CONTENTS EDLQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EDLQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tnL Dlo E•MA Features Heating only monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 140 • AlthermaTM • Monobloc
• Monobloc • EDLQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 Heating capacity Nominal kW 11.20 14.00 16.00 Heating PI Nominal kW 2.51 3.22 3.72 COP Nominal 4.46 4.35 4.30 Heating capacity Nominal kW 10.87 13.10 15.06 Heating PI Nominal kW 3.12 3.98 4.58 COP Nominal 3.48 3.29 3.
• Monobloc • EDLQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Air heat exchanger Specifications Length EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 857 857 857 2 2 2 mm 1.4 1.4 1.4 5 5 5 m² 1.131 1.131 1.
• Monobloc • EDLQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply compressor component Main Power Voltage range EDLQ011AA6W1 EDLQ014AA6W1 Name W1 Phase 3N~ EDLQ016AA6W1 Frequency Hz 50 50 50 Voltage V 400 400 400 Minimum V -10% Maximum V +10% Nominal running current (RLA) Heating (A) A 5.8 5.8 5.
• Monobloc • EDLQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EDLQ011AA6W1 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EDLQ016AA6W1 -10% Quantity of wires 3 EDLQ014AA6W1 3G Type of wires
• Monobloc • EDLQ011-016AA6W1 3 Options EDLQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EDLQ011-016AA6W1 3 Options EDLQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EDLQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EDLQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EDLQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EDLQ011-016AA6W1 3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EDLQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EDLQ011-016AA6W1 Expansion vessel Filter Pressure gauge Filter Evaporator Condenser Safety valve Heat exchanger Distributor 3 Air purge 6 Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor
• Monobloc • EDLQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EDLQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.
• Monobloc • EDLQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EDLQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off indication, solar interlock) X1M: L1-L2-L3-N-Earth or L-N-Earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater
• Monobloc • EDLQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EDLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EDLQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EDLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EDLQ011-016AA6W1 9 Installation 9-1 Service space EDLQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle 3 Left side obstacle 9 Right side obstacle Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EDLQ011-016AA6W1 10 Operation range Outdoor temp. (°CDB) Cooling mode EDLQ011-016AA6W1 3 only EB(H/L)* 10 Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDLQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EDLQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EBHQ011-016AA6V3 TABLE OF CONTENTS EBHQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EBHQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tHn Blo E•MA Features Reversible monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 158 • AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.47 3.20 3.79 Cooling PI Nominal kW 3.78 5.65 6.28 COP Nominal 4.54 4.37 4.22 EER Nominal 3.39 2.83 2.66 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.
• Monobloc • EBHQ011-016AA6V3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBHQ011AA6V3 Type Charged Volume l 1.0 2 EBHQ016AA6V3 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBHQ014AA6V3 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit.
• Monobloc • EBHQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.
• Monobloc • EBHQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EBHQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 3G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBHQ016AA6V3 -10% Quantity of wires 3 EBHQ014AA6V3 3G Type of wires
• Monobloc • EBHQ011-016AA6V3 3 Options EBHQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 1-Phase Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 Reference Description EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2) V
• Monobloc • EBHQ011-016AA6V3 3 Options EBHQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EBHQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EBHQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EBHQ011-016AA6V3 4 Capacity tables 4-2 Cooling capacity tables EBHQ011-016AA6V3 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 166 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc.
• Monobloc • EBHQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBHQ011-016AA6V3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EBHQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EBHQ011-016AA6V3 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermi
• Monobloc • EBHQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EBHQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.
• Monobloc • EBHQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EBHQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Onl
• Monobloc • EBHQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EBHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EBHQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EBHQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EBHQ011-016AA6V3 9 Installation 9-1 Service space EBHQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EBHQ011-016AA6V3 10 Operation range EBHQ011-016AA6V3 Outdoor temp. (°CDB) 10 Cooling mode 3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBHQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EBHQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EBHQ011-016AA6W1 TABLE OF CONTENTS EBHQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EBHQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hoQ tHn Blo E•MA Features Reversible monobloc • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 178 • AlthermaTM • Monobloc
• Monobloc • EBHQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.51 3.22 3.72 Cooling PI Nominal kW 3.78 5.32 6.06 COP Nominal 4.46 4.35 4.30 EER Nominal 3.39 3.01 2.76 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.
• Monobloc • EBHQ011-016AA6W1 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBHQ011AA6W1 Type Charged Volume l 1.0 2 EBHQ016AA6W1 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBHQ014AA6W1 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit.
• Monobloc • EBHQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer Drain valve / Fill valve yes Shut off valve yes l 5.
• Monobloc • EBHQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component EBHQ011AA6W1 Voltage range Minimum V Maximum V Wiring connections Connection type +10% for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBHQ016AA6W1 -10% Quantity of wires 3 EBHQ014AA6W1 3G Type of wires
• Monobloc • EBHQ011-016AA6W1 3 Options EBHQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EBHQ011-016AA6W1 3 Options EBHQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EBHQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EBHQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EBHQ011-016AA6W1 4 Capacity tables 4-2 Cooling capacity tables EBHQ011-016AA6W1 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 186 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc.
• Monobloc • EBHQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBHQ011-016AA6W1 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EBHQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EBHQ011-016AA6W1 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (
• Monobloc • EBHQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EBHQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.
• Monobloc • EBHQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EBHQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Onl
• Monobloc • EBHQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EBHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EBHQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EBHQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EBHQ011-016AA6W1 9 Installation 9-1 Service space EBHQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EBHQ011-016AA6W1 10 Operation range 10 Outdoor temp. (°CDB) 3 Cooling mode EBHQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBHQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EBHQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EBLQ011-016AA6V3 TABLE OF CONTENTS EBLQ011-016AA6V3 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EBLQ011-016AA6V3 1 A A 6 1 0 ac- mo1 r l1 eb0 hQo tLn Blo E•MA Features Reversible monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 198 • AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6V3 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.47 3.20 3.79 Cooling PI Nominal kW 3.78 5.65 6.28 COP Nominal 4.54 4.37 4.22 EER Nominal 3.39 2.83 2.66 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.
• Monobloc • EBLQ011-016AA6V3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBLQ011AA6V3 Type Charged Volume l 1.0 2 EBLQ016AA6V3 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBLQ014AA6V3 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit.
• Monobloc • EBLQ011-016AA6V3 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.
• Monobloc • EBLQ011-016AA6V3 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component Voltage range Wiring connections EBLQ011AA6V3 Minimum V Maximum V +10% Connection type for power supply hydraulic compartment 3G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBLQ016AA6V3 -10% Quantity of wires 3 EBLQ014AA6V3 3G Type of wires
• Monobloc • EBLQ011-016AA6V3 3 Options EBLQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase Reference Description Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EBLQ011-016AA6V3 3 Options EBLQ011-016AA6V3 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EBLQ011-016AA6V3 4 Capacity tables 4-1 Heating capacity tables EBLQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EBLQ011-016AA6V3 4 Capacity tables 4-2 Cooling capacity tables EBLQ011-016AA6V3 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 206 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc.
• Monobloc • EBLQ011-016AA6V3 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBLQ011-016AA6V3 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EBLQ011-016AA6V3 6 Piping diagram 6-1 Piping diagram EBLQ011-016AA6V3 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Flowswitch Filter Inlet Shut off valve Accumulator Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (discharge) Thermistor (Suction) Thermistor (Liquid 1) Thermi
• Monobloc • EBLQ011-016AA6V3 7 Wiring diagram 7-1 Wiring diagram EBLQ011-016AA6V3 Power supply A1P A2P A3P A4P BS1∼BS4 C1∼C4 DS1 E1H E1HC F1U, F3U, F4U F6U F7U, F8U H1P∼7P (A2P) Compressor module switchbox N-50Hz 230V Only for E(D/B)LO* To hydromodule switchbox (8.5 Page 2 Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Bottomplate heater Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.
• Monobloc • EBLQ011-016AA6V3 7 Wiring diagram 7-2 External connection diagram EBLQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Onl
• Monobloc • EBLQ011-016AA6V3 8 Sound data 8-1 Sound pressure spectrum EBLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EBLQ011-016AA6V3 8 Sound data 8-2 Sound pressure night quiet mode EBLQ011-016AA6V3 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EBLQ011-016AA6V3 9 Installation 9-1 Service space EBLQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EBLQ011-016AA6V3 10 Operation range EBLQ011-016AA6V3 Outdoor temp. (°CDB) 10 Cooling mode 3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBLQ011-016AA6V3 11 Hydraulic performance 11 - 1 Static pressure drop unit EBLQ011-016AA6V3 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
• Monobloc • EBLQ011-016AA6W1 TABLE OF CONTENTS EBLQ011-016AA6W1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Monobloc • EBLQ011-016AA6W1 1 A A 6 1 0 ac- mo1 r l1 eb0 hQo tLn Blo E•MA Features Reversible monobloc with bottom plate heater • Low energy bills and low CO2 emissions • H2O piping between outdoor unit and indoor heating appliances • Easy to install • Freeze protection of hydraulic parts • Total solution for year round comfort • Cost effective alternative to a fossil fuel boiler 3 1 218 • AlthermaTM • Monobloc
• Monobloc • EBLQ011-016AA6W1 2 2-1 Specifications NOMINAL CAPACITY AND NOMINAL INPUT Condition 1 Condition 2 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Heating capacity Nominal kW 11.20 14.00 16.00 Cooling capacity Nominal kW 12.85 15.99 16.73 Heating PI Nominal kW 2.51 3.22 3.72 Cooling PI Nominal kW 3.78 5.32 6.06 COP Nominal 4.46 4.35 4.30 EER Nominal 3.39 3.01 2.76 Heating capacity Nominal kW 10.87 13.10 15.06 Cooling capacity Nominal kW 10.00 12.50 13.
• Monobloc • EBLQ011-016AA6W1 2 2-2 Specifications TECHNICAL SPECIFICATIONS Refrigerant Oil EBLQ011AA6W1 Type Charged Volume l 1.0 2 EBLQ016AA6W1 1.0 Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method 3 EBLQ014AA6W1 Daphne FVC68D 1.0 Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Notes The sound pressure level is measured via a microphone at a certain distance from the unit.
• Monobloc • EBLQ011-016AA6W1 2 2-3 Specifications MAIN COMPONENTS Expansion vessel Water filter EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Volume l 10 10 10 Maximum water pressure bar 3 3 3 Pre pressure bar 1.0 1.0 1.0 Diameter perforations mm 1 1 1 Material Water circuit Brass Piping connections inch Piping inch Safety valve bar G5/4 (FEMALE) 5/4" 3 Manometer Drain valve / Fill valve yes Shut off valve yes l ELECTRICAL SPECIFICATIONS Main Power 5.5 5.5 5.
• Monobloc • EBLQ011-016AA6W1 2 2-4 Specifications ELECTRICAL SPECIFICATIONS Power supply hydraulic component EBLQ011AA6W1 Voltage range Minimum V Maximum V Wiring connections Connection type +10% for power supply hydraulic compartment 4G Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires 2 EBLQ016AA6W1 -10% Quantity of wires 3 EBLQ014AA6W1 3G Type of wires
• Monobloc • EBLQ011-016AA6W1 3 Options EBLQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature Zone 2 EDLQ***AA6V3 EBLQ***AA6V3 011 014 016 1-Phase Zone 3 EDHQ***AA6V3 EBHQ***AA6V3 011 014 016 3-Phase Zone 2 Zone 3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6W1 EBHQ***AA6W1 011 014 016 011 014 016 Reference Description EKRP1HB Digital I/O PCB V V V V V V V V V V V V EKBPHT16Y Bottom plate heater - - - V (2) V (2) V (2) - - - V (2) V (2)
• Monobloc • EBLQ011-016AA6W1 3 Options EBLQ011-016AA6W1 Field wiring Bivalent system Space heating with an auxiliary boiler (alternating operation) 3 3 Space heating application by either the altherma indoor unit or by an auxiliary boiler connected in the system. An auxiliary contact decides whether either the E(D/B)(H/L)Q* hydro module or the boiler will operate.This auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc.
• Monobloc • EBLQ011-016AA6W1 4 Capacity tables 4-1 Heating capacity tables EBLQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb 30 HC [kW] 35 PI [kW] HC [kW] 40 PI [kW] HC [kW] 45 PI [kW] HC [kW] 50 PI [kW] HC [kW] 55 PI [kW] HC [kW] PI [kW] 3 4 Maximum Heating Capacity (integrated values) Model LWC Tamb 30 HC 35 PI HC 40 PI HC 45 PI HC 50 PI HC 55 PI HC PI 3TW58012-1A SYMBOLS CC NOTES PI LWE LWC Tamb : Cooling capacity at maximum operating fre
• Monobloc • EBLQ011-016AA6W1 4 Capacity tables 4-2 Cooling capacity tables EBLQ011-016AA6W1 Maximum Cooling Capacity Model Tamb LWE [°C] 20 CC [kW] 25 PI [kW] CC [kW] 30 PI [kW] CC [kW] 35 PI [kW] CC [kW] 40 PI [kW] CC [kW] 45 PI [kW] CC [kW] PI [kW] 3 4 3TW58012-1A SYMBOLS CC PI LWE LWC Tamb (a) : only E(D/B)L* HC 226 NOTES : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc.
• Monobloc • EBLQ011-016AA6W1 5 Dimensional drawing & centre of gravity 5-1 Dimensional drawing EBLQ011-016AA6W1 Hole for anchor bolt 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 13. 14. 15. 16. 17. 18. 19. 20. 21.
• Monobloc • EBLQ011-016AA6W1 6 Piping diagram 6-1 Piping diagram EBLQ011-016AA6W1 Expansion vessel Filter Pressure gauge Evaporator Condenser Safety valve 3 6 Filter Heat exchanger Distributor Air purge Pump Outlet Shut off valve Service port 5/16″ Electric heater body Capillary tube Flowswitch Filter Inlet Shut off valve Accumulator Stop valve (with service port 5/16’ flare) Drain & fill valve R1T R2T R3T R4T R5T R6T S1NPH Y1E E1HC : : : : : : : : : Thermistor (Air) Thermistor (
• Monobloc • EBLQ011-016AA6W1 7 Wiring diagram 7-1 Wiring diagram EBLQ011-016AA6W1 Power supply Compressor module switchbox To hydromodule switchbox (8.
• Monobloc • EBLQ011-016AA6W1 7 Wiring diagram 7-2 External connection diagram EBLQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring diagram Standard parts Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth Bottom plate heater option Optional power supply X1M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth Field supply Onl
• Monobloc • EBLQ011-016AA6W1 8 Sound data 8-1 Sound pressure spectrum EBLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC)
• Monobloc • EBLQ011-016AA6W1 8 Sound data 8-2 Sound pressure night quiet mode EBLQ011-016AA6W1 E(D/B)(H/L)Q016* HEATING Sound pressure level (dB) Sound pressure level (dB) E(D/B)(H/L)Q014* HEATING Sound pressure level (dB) E(D/B)(H/L)Q011* HEATING 3 8 Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: 1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according
• Monobloc • EBLQ011-016AA6W1 9 Installation 9-1 Service space EBLQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle 3 Right side obstacle 9 Top side obstacle Obstacle is present 1 2 In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed.
• Monobloc • EBLQ011-016AA6W1 10 Operation range 10 Outdoor temp. (°CDB) 3 Cooling mode EBLQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity Outdoor temp. (°CDB) Heating mode (*) E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBLQ011-016AA6W1 11 Hydraulic performance 11 - 1 Static pressure drop unit EBLQ011-016AA6W1 3 ESP (kPa) 11 I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit Flow (l/min) WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.
EEDEN09-720 technical data AlthermaTM Part 4/4: EKHWS-B EKHWE EKSOLHWAV1 EKRTW EKRTR
• Domestic hot water tank • EKHWS-B TABLE OF CONTENTS EKHWS-B 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . .
• Domestic hot water tank • EKHWS-B 1 o h c a i m Bt r - s e S e h W mtH oKl •DEA Features Stainless steel domestic hot water tank • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 4 1 240 • AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWS-B 2 2-1 Specifications TECHNICAL SPECIFICATIONS Casing Dimensions Packing EKHWS200B 3V3 EKHWS300B 3V3 EKHWS200B 3Z2 EKHWS300B 3Z2 Colour Neutral white Material Epoxy-coated mild steel Packing Unit Weight EKHWS150B 3V3 EKHWSU150 B3V3 EKHWSU200 B3V3 EKHWSU300 B3V3 1,735 Height mm 950 1,200 1,650 1,200 1,650 1,040 1,280 Width mm 600 600 600 600 600 600 600 600 Depth mm 600 600 600 600 600 600 600 600 Height mm 900 1,150 1,6
• Domestic hot water tank • EKHWS-B 3 Capacity tables 3-1 Cooling capacity tables The ALTHERMA by Daikin heat pump in combination with the optional domestic hot water tank provide hot water for household usage. The below mentioned date allow a proper selection of the domestic hot water tank size for maximum comfort and efficiency.
• Domestic hot water tank • EKHWS-B 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHWS-B j 1 Water mains in G 3/4 (Female) j 2 Water mains out G 3/4 (Female) j 3 Thermistor connection j 4 Flow (from EKHB(H/X)*) G 3/4 (Female) j 5 Return (to EKHB(H/X)*) G 3/4 (Female) j 6 Switchbox j 7 Thermal protector j 8 Anode j 9 Cable entry: power, booster heater and thermal protection cable j 10 Re-circulation connection: G 3/4 (Female) j 11 Cable entry for EKSOLHWAV1: power supply from EKHB(H
• Domestic hot water tank • EKHWS-B 5 Piping diagram EKHWSU-B Overview Field installation (delivered with indoor unit) Field installation (Delivered with EKHWSU*B*) 3-way motorized valve Shut off valve Outdoor Load Indoor Shut off valve Water return Water flow Option domestic hot water tank 4 Water flow Water return 5 Option domestic hot water tank Water main OUT Water main IN Pressure reducing valve with integrated non return valve line strainer Expansion relief valve T-piece 2-way sole
• Domestic hot water tank • EKHWE TABLE OF CONTENTS EKHWE 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . .
• Domestic hot water tank • EKHWE 1 o h c a i m t r s e E e h W mtH oKl •DEA Features Enameled domestic hot water tank • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 4 1 246 • AlthermaTM • Domestic hot water tank
• Domestic hot water tank • EKHWE 2 2-1 Specifications TECHNICAL SPECIFICATIONS Mounting Casing EKHWE150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 EKHWET150A3V3 Floor Floor Floor Floor Floor Wall Colour RAL9010 Material Dimensions Packing Unit Epoxy coated steel Height mm 1,460 1,835 1,830 1,835 1,830 1,460 Width mm 615 615 720 615 720 615 Depth mm 625 625 730 625 730 625 Height mm 1,205 1,580 1,572 1,580 1,572 1,205 545 Diameter Weight Pack
• Domestic hot water tank • EKHWE 3 Capacity tables 3-1 Cooling capacity tables The ALTHERMA by Daikin heat pump in combination with the optional domestic hot water tank provide hot water for household usage. The below mentioned date allow a proper selection of the domestic hot water tank size for maximum comfort and efficiency.
• Domestic hot water tank • EKHWE 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKHWE Required service space around the tank Wall mounted j 1 Cold water inlet: G 3/4 (Male) j 2 Hot water outlet: G 3/4 (Male) j 3 Thermistor hole j 4 Flow (From EKHB(H/X)*): Rp 3/4 (Female) j 5 Return (To EKHB(H/X)*): Rp 3/4 (Female) j 6 Switchbox j 7 Thermal protector j 8 Anode j 9 Cable entry j 10 Re-circulation connection: G 3/4 (Male) j 11 Thermistor hole (See EKSOLHWAV1) j 12 Wall plate 150L Wa
• Domestic hot water tank • EKHWE 5 Wiring diagram 5-1 Wiring diagram EKHWE *KHBH/X* Switchbox *KHBH/X* Switchbox *KHWE**0A3V3 Water tank Switchbox *KHWE**00A3Z2 Water tank Switchbox Setpoint Q2L & Q3L: 89°C Setpoint Q2L: 89°C 4 5 E4H F2B K3M L N Q2L Q3L X2M∼X4M X9M∼X10M : Booster heater : Fuse booster heater : Contactor booster heater : Line : Neutral : Thermal protector Booster heater : Thermal protector 2 Hot water tank : Terminal block : Terminal block Solar pump Solar pump EKSOLHWAV1 (Op
• Solar Kit • EKSOLHWAV1 TABLE OF CONTENTS EKSOLHWAV1 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Solar Kit • EKSOLHWAV1 1 t 1 i V aKA m W r H r e L a hO l tS oKl E•SA Features Connectable to solar collectors • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort • Low energy bills and low CO2 emissions 4 1 252 • AlthermaTM • Solar Kit
• Solar Kit • EKSOLHWAV1 2 2-1 Specifications TECHNICAL SPECIFICATIONS Dimensions Packing Unit Weight Packing Height mm Width mm 340 Depth mm 295 Pump 795 Height mm 770 Width mm 305 Depth mm 270 Unit kg 8 Packed Unit kg 9 Material Carton Weight Heat Exchanger EKSOLHWAV1 kg Type 1 4 Brazed plate 2 Pressure drop Solar side kPa 21.
• Solar Kit • EKSOLHWAV1 3 Dimensional drawing & centre of gravity 3-1 Dimensional drawing EKSOLHWAV1+EKHWS EKSOLHWAV1 + EKHWS200-300* EKSOLHWAV1 + EKHWS150* 4 Detail 1 Detail 1 3 Switchbox domestic hot water tank j 11 Cable entry (Altherma indoor unit) j 12 Cable entry (Pump cable) Components j 1 j 2 j 3 j 4 Pump + switch for speed setting Heat exchanger EPP casing Non return valves Accessories (delivered with EKSOLHWAV1) Connection type j 13 Thermistor sockel (thermistor solar pump station)
• Solar Kit • EKSOLHWAV1 3 Dimensional drawing & centre of gravity 3-1 Dimensional drawing EKSOLHWAV1+EKHWSU EKSOLHWAV1 + EKHWS200-300* EKSOLHWAV1 + EKHWS150* Detail 2 Scale: 1/4 Detail 2 4 Detail 1 3 Switchbox domestic hot water tank j 11 Cable entry (Altherma indoor unit) j 12 Cable entry (Pump cable) Components j 1 j 2 j 3 j 4 Pump + switch for speed setting Heat exchanger EPP casing Non return valves Accessories (delivered with EKSOLHWAV1) Connection type j 13 Thermistor sockel (thermist
• Solar Kit • EKSOLHWAV1 4 Piping diagram EKSOLHWAV1 Overview Indoor 3-way motorized valve Load Shut off valve Shut off valve Water from indoor Field supply Solar collector Option domestic hot water tank Field supply Solar pump station 4 Solenoid valve 3-way motorized valve Field supply Field installation (delivered with indoor unit) Outdoor Y1S M3S Water to tank Medium from solar collector Option solar kit Medium to solar collector Water from tank 4 * Delivered with EKUHWA kit Water
• Solar Kit • EKSOLHWAV1 5 Wiring diagram 5-1 Wiring diagram EKSOLHWAV1 with EKHWS*V3 EKHWS*V3 Switchbox EKHB/X* Switchbox Solar pump 4 5 EKHB/X* Switchbox E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S : Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block :
• Solar Kit • EKSOLHWAV1 5 Wiring diagram 5-1 Wiring diagram EKSOLHWAV1 with EKHWSU EKHWS*V3 Switchbox EKUHWA EKHB/X* Switchbox 4 Notes: 1 5 2 3 : Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual.
• Room thermostat • • EKRTW TABLE OF CONTENTS EKRTW 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Room thermostat • EKRTW 1 Features s o m r e a h m t r e W mh T otR oKl EAR 4 1 260 • AlthermaTM • Room thermostat
• Room thermostat • EKRTW 2 2-1 Specifications TECHNICAL SPECIFICATIONS Dimensions Unit Packing Weight Unit Packing EKRTW Height mm 87 Width mm 125 34 Depth mm Height mm 65 Width mm 175 Depth mm 100 Net g 215 Gross g 440 Material Carton Weight g 55 4 Ambient temperature Storage °C -20~60 Operation °C 0~50 2 Temperature setting range Heating °C 4-37 Cooling °C 4-37 Temperature setting resolution °C Clock 0.
• Room thermostat • EKRTW 3 Options Additional information: comfort function mode reduced function mode scheduled function mode holiday function mode off function setpoint limitation floor temperature protection Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode) Use this mode for a fixed temperature on reduced level.
• Room thermostat • EKRTW 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKRTW 4 4 EKRTR 4TW57994-1 • AlthermaTM • Room thermostat 263
• Room thermostat • EKRTR TABLE OF CONTENTS EKRTR 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Room thermostat • EKRTR 1 Features s o m r e a h m t r e R mh T otR oKl EAR 4 1 266 • AlthermaTM • Room thermostat
• Room thermostat • EKRTR 2 2-1 Specifications TECHNICAL SPECIFICATIONS Dimensions Unit Packing Weight Unit Packing EKRTR thermostat Height mm 87 Width mm 125 34 Depth mm Height mm 70 Width mm 200 Depth mm 140 Net g 210 Gross g 665 Material Carton Weight g 85 4 Ambient temperature Storage °C -20~60 Operation °C 0~50 2 Temperature setting range Heating °C 4-37 Cooling °C 4-37 Temperature setting resolution °C Clock 0.
• Room thermostat • EKRTR 3 Options Additional information: comfort function mode reduced function mode scheduled function mode holiday function mode off function setpoint limitation floor temperature protection Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode) Use this mode for a fixed temperature on reduced level.
• Room thermostat • EKRTR 4 Dimensional drawing & centre of gravity 4-1 Dimensional drawing EKRTW 4 4 EKRTR 4TW57994-1 • AlthermaTM • Room thermostat 269