10 Operation range
3
10
4TW58133-1A
EBHQ011-016AA6W1
Outdoor temp. (°CDB)
Cooling mode
Heating mode
Sanitary mode
Outdoor temp. (°CDB)Outdoor temp. (°CDB)
Leaving evaporator
Water temperature (°C)
No heat pump operation, back up heater only
operation possible, but no guarantee of capacity
(*) E(D/B)L* units include special equipment (insulation, heater
sheet,...)toensure good operation in areas where low
ambient temperature can occur together with high
humidity conditions. In such conditions the E(D/B)H*
models may experience problems with severe ice build-up
on the aircooled coil. In case such conditions are expected,
the E(D/B)L* must be installed instead.
Both E(D/B)L* and E(D/B)H* models have a freeze
prevention function using the pump and back up heater to
keep the water system safe from freezing in all conditions.
In case accidental or intentional power shutdown is likely
to happen we recommend to use glycol.
(**) only E(D/B)L*
Leaving condenser water temperature
Water temperature sanitary tank (C°)
Booster heater operation only
(**) only E(D/B)L*
only EB(H/L)*