damage to the compressor. You can also set
this value to determine when you want the
auxiliary heat (if installed) to engage to help
meet the set temperature. The temperature
range is adjustable from –10 to 65 °F (–23.3 to
18.3 °C) or disabled by default.
This feature uses the Internet to obtain the
current outdoor temperature. If no Internet is
available, the Outdoor Unit’s temperature sensor
is used instead.
Cool Dierential Temp The minimum
dierence between the current temperature
and set temperature before the system calls
for cool. A smaller dierence means shorter
cycle times, whereas a larger dierence results
in longer cycle times. The temperature range
is adjustable from 0.5 to 3 °F (0.3 to 1.7 °C) in
0.5°F (0.3°C) increments.
Cool Dissipation Time The amount of time
the fan will run after the cool has been turned
o. Running the fan for a period of time allows
for any cooled air left in the ducts to circulate
throughout the home. The time is adjustable
from 0 to 900 seconds (default is 0 seconds).
AC Overcool Max When using the AC to
dehumidify, the setting congures how
many degrees below the current set point
the thermostat will run in order to reach the
dehumidify set point. Options are Disabled
(default) and 0.5 to 3 °F (0.3 to 1.8°C) in 0.5 F
(0.3°C) increments.
Heat Dierential Temp The minimum
dierence between the current temperature
and set temperature before the system calls
for heat. A smaller dierence means shorter
cycle times, whereas a larger dierence results