Installation manual

Above this level, the auxiliary heat will not be
activated. The temperature is adjustable from 0
to 80 °F (-17.8 to 26.5 °C) in increments of 0.5°F
(0.3°C). The default value is 70°F (21°C).
Fan Conguration
The Fan Conguration settings map the Indoor
Unit’s internal fan speeds to the fan speed options
displayed to the user on the thermostat.
Heating Mode Speeds Congures fan speed
when the user selects High, Medium or Low
while the system is in heat mode. The possible
speeds for each value are High, Medium High,
Medium, Medium Low, and Low.
Cooling Mode Speeds Congures fan speed
when the user selects High, Medium or Low
while the system is in cool mode. The possible
speeds for each value are High, Medium High,
Medium, Medium Low, and Low.
Fan Only Mode Speeds Congures fan speed
when the user selects High, Medium or Low
while the system is not actively cooling or
heating the room. The possible speeds for
each value are High, Medium High, Medium,
Medium Low, and Low.
Aux Fan Min Speed Congures minimum fan
speed used when Aux Heat requires a fan. The
possible speed is High, Medium High, Medium,
Medium Low, or Low.
Force System O
Force System O is used to clear a latched system
error status in the indoor unit by turning o the
equipment for ve seconds after system servicing.
Operation will automatically resume with the
previous settings once complete.
21