00_CV_3PN14093-12A.fm Page 1 Friday, September 2, 2011 10:45 AM INSTALLATION MANUAL SPLIT SYSTEM Air Conditioners MODELS Ceiling-mounted Duct type FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU FBQ42PVJU English Français Español Read these instructions carefully before installation. Keep this manual in a handy place for future reference. Lire soigneusement ces instructions avant l’installation. Conserver ce manuel à portée de main pour référence ultérieure.
00_CV_3PN14093-12A.
01_EN_3PN14093-12A.fm Page 1 Friday, September 16, 2011 6:40 PM SPLIT SYSTEM Air Conditioners CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. SAFETY CONSIDERATIONS .......................................... 1 BEFORE INSTALLATION ................................................ 3 SELECTING INSTALLATION SITE .................................. 4 PREPARATIONS BEFORE INSTALLATION ................... 5 INDOOR UNIT INSTALLATION........................................ 6 REFRIGERANT PIPING WORK...........................
01_EN_3PN14093-12A.fm Page 2 Friday, September 16, 2011 6:40 PM • Before touching electrical parts, turn off the unit. • Be sure to install a ground fault circuit interrupter if one is not already available. This helps prevent electrical shocks or fire. • Securely fasten the outdoor unit terminal cover (panel). If the terminal cover/panel is not installed properly, dust or water may enter the outdoor unit causing fire or electric shock.
01_EN_3PN14093-12A.fm Page 3 Friday, September 16, 2011 6:40 PM 2. BEFORE INSTALLATION • When moving the unit while removing it from the carton box, be sure to lift it by holding on to the four lifting lugs without exerting any pressure on other parts, especially, the refrigerant piping, drain piping, flanges and other resin parts. • Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect refrigerant will prevent normal operation of the unit.
01_EN_3PN14093-12A.fm Page 4 Friday, September 16, 2011 6:40 PM 2-3 OPTIONAL ACCESSORIES b. Items to be checked at time of delivery • These is one type of remote controller: wired. Items to be checked NOTE Are you sure the control box cover, air filter, air inlet grille, and air outlet grille are mounted? • If you wish to use a remote controller that is different from the above, select a suitable remote controller after consulting catalogs and technical materials.
01_EN_3PN14093-12A.fm Page 5 Friday, September 16, 2011 6:40 PM CAUTION (length: in.) Case 1 *H3=Min. 12 Control box Inspection hatch Ceiling 28 24-13/16 (Suspension bolt pitch) (2) Use suspension bolts to install the indoor unit. Check that the place of installation withstands the weight of the indoor unit. Secure the suspension bolts with proper beams if necessary. (Suspension bolt pitch) Suspension bolt (× 4) Fig. 2-2 Case 2, 3 Inspection hatch (Ceiling opening) Control box Min.
01_EN_3PN14093-12A.fm Page 6 Friday, September 16, 2011 6:40 PM (2) Mount the canvas ducts to the air outlet and inlet so that the vibration of the air conditioner will not be transmitted to the duct or ceiling. Apply a sound-absorbing material (insulation material) to the inner wall of the duct and vibration insulation rubber to the suspension bolts (refer to 8. DUCT WORK). (3) Open installation holes (if the ceiling already exists). • Open the installation holes on the ceiling.
01_EN_3PN14093-12A.fm Page 7 Friday, September 16, 2011 6:40 PM CAUTION • Use the level and check that the unit is installed horizontally. (4-directions) • In the case of using a vinyl tube (filled with water) in place of the level, align the bottom of the unit to the water surface at both edges of the vinyl tube to make levelness adjustment. If the unit is installed at a slant with the drain pipe side set high, in particular, the float switch will not operate normally and water leakage may result.
01_EN_3PN14093-12A.fm Page 8 Friday, September 16, 2011 6:40 PM Table 2 Pipe size Further tightening angle Recommended arm length of tool φ 1/4 60 to 90 degrees Approx. 5-7/8 in. φ 3/8 60 to 90 degrees Approx. 7-7/8 in. φ 1/2 30 to 60 degrees Approx. 9-13/16 in. φ 5/8 30 to 60 degrees Approx. 11-13/16 in. (2) On completion of installation work, check that there is no gas leakage.
01_EN_3PN14093-12A.fm Page 9 Friday, September 16, 2011 6:40 PM • The drain piping will be clogged with water and water leakage may result if the water is accumulated in the drain piping. • Select the diameter of the concentrated drain piping to suit the capacity of equipment connecting to the concentrated drain piping (see the equipment design sheet). Ceiling slab 12 in. max. • Conduct drain-up piping work if the gradient is insufficient. • Attach a support bracket at 3.3 to 4.
01_EN_3PN14093-12A.fm Page 10 Friday, September 16, 2011 6:40 PM The drainage can be checked with the water level change in the drain pan through the water inlet. CAUTION • Do not touch the drain pump. Otherwise, an electric shock may be received. • Do not impose external force on the float switch. Otherwise, a failure may result. 5. On completion of the drainage check, shut off the power supply and disconnect the power supply line. 6. Put the control box cover to the original position.
01_EN_3PN14093-12A.fm Page 11 Friday, September 16, 2011 6:40 PM 9. 9-1 ELECTRIC WIRING WORK 9-3 GENERAL INSTRUCTIONS • All field supplied parts and materials and electric works must conform to local codes. • Use copper wire only. • For electric wiring work, refer to also “Wiring diagram” attached to the control box cover. • For remote controller wiring details, refer to the installation manual attached to the remote controller. • All wiring must be performed by an authorized electrician.
01_EN_3PN14093-12A.fm Page 12 Friday, September 16, 2011 6:40 PM (2) Lay the wires in the control box through the wire inlet on the side of the control box. Elbow (Field supply) Lock nut (Field supply) Conduit (Field supply) Low-voltage wiring inlet Transmission wiring (Low voltage) Remote controller wiring (Low voltage) (3) Follow the instructions below, and lay the wires in the control box. Fix the wires with clamp (8) to the wire fixing bracket provided to the control box.
01_EN_3PN14093-12A.fm Page 13 Friday, September 16, 2011 6:40 PM (4) Put the control box cover, and wrap the wire sealing material (Small) (10) around the conduit so as to block the wire through holes. Wire through holes 10-2 WIRING EXAMPLE WARNING Install a ground fault circuit interrupter. The installation of a ground fault circuit interrupter is imperative for the prevention of electric shocks and fire accidents.
01_EN_3PN14093-12A.fm Page 14 Friday, September 16, 2011 6:40 PM 2. When using 2 remote controllers Power Supply 208/230V 1 ~ 60Hz (2) Set the main/sub switch on one of the remote controller PCBs to sub. (Keep the switch of the other remote controller PCB set to main.
01_EN_3PN14093-12A.fm Page 15 Friday, September 16, 2011 6:40 PM 11. FIELD SETTING Make sure the control box covers are closed on the indoor and outdoor units. Field setting must be made from the remote controller in accordance with the installation conditions. • Setting can be made by changing the “Mode No.”, “FIRST CODE NO.”, and “SECOND CODE NO.”. • For setting procedures and instructions, refer to the “FIELD SETTING” in the installation manual of the remote controller.
01_EN_3PN14093-12A.fm Page 16 Friday, September 16, 2011 6:40 PM 12. TEST RUN Table 4 External Static Pressure Mode No. FIRST CODE NO. SECOND CODE NO. 0.20 inWG 02 0.24 inWG 03 0.28 inWG 04 0.32 inWG 05 0.36 inWG 06 0.40 inWG 07 0.44 inWG 13 (23) 0.48 inWG 08 06 09 0.52 inWG 10 0.56 inWG 11 0.60 inWG 12 0.64 inWG 13 0.72 inWG 14 0.80 inWG 15 Refer to the installation manual of the outdoor unit.
00_CV_3PN14093-12A.fm Page 3 Friday, September 2, 2011 10:45 AM 1645 Wallace Drive, Suite 110 Carrollton, TX 75006 USA info@daikinac.com www.daikinac.